6-14
(2) JW-22PU (DC power supply module)
- Ensure correct connection for polarity of the input power supply. Mis-connection of the polarity will
destroy the module when power is supplied.
- As for DC input power supply, use power supply of 20.4 to 32 VDC (ripple rate 20% or less;
however, ripple upper limit: 32 V or less, lower limit: 20.4 V or more).
(3) JW-303PU (AC power supply module)
- Connect the power supply input to the L terminal (LIVE: ungrounded side) and N terminal
(NEUTRAL: grounded side) while paying attention.
POWER
RUN
DC power supply
(20.4 to 32V)
Halt output
Be sure to connect the
line to the emergency
stop circuit.
Ground line
To prevent electric shock and noise
error, be sure to separately prepare
class-D ground.
85 to 264VAC
Halt output
Be sure to connect
the terminals to the
emergency stop circuit.
Ground
POWER
RUN
JW-303PU
L
N
POWER
INPUT
100∼240VAC
GND
HALT
OUTPUT
1A
100∼240VAC
(24VAC)
External ground
Noise filter
Install a noise filter to prevent
from entering noise on the power
supply lines and noise from the
power supply module.
- To prevent electric shock and malfunctions
due noise, be sure to establish a separate
class-D ground.
- If you cannot make a separate ground,
connect the ground terminal directly to the