Thank you for purchasing the ME-NET module (JW-21MN) for the SHARP programmable controller. Read this manual thoroughly to completely familiarize yourself with the operation according to the examples. Keep this manual for future reference. We are confident that this manual will be helpful whenever you encounter a problem. Note - This manual describes the JW-21MN that will be compatible with the JW30H. The JW-21MN that is applied to JW30H has a 30Hn mark in front of the module.
Safety Precautions Read this manual and attached documents carefully before installation, operation, maintenance and checking in order to use the machine correctly. Understand all of the machine knowledge, safety information, and cautions before starting to use. In this instruction manual, safety precautions are ranked into "danger" and "caution" as follows. Danger : Wrong handling may possibly lead to death or heavy injury. Caution : Wrong handling may possibly lead to medium or light injury.
3) Use Danger - Don't touch the terminal while the power is being supplied or you may have an electric shock. - Assemble the emergency stop circuit and interlock circuit outside of the programmable controller. Otherwise breakdown or accident damage of the machine may be caused by the trouble of the programmable controller. Caution - "RUN" or "STOP" during operation should be done with particular care by confirming safety. Misoperation may lead to damage or accident of the machine.
ME-NET Module: JW-21MN - User's Manual Chapter 1 Features and Functions Chapter 2 Safety Precautions Chapter 3 System Configuration Chapter 4 Name and Function of Each Part Chapter 5 Installation Chapter 6 Processing of Cables Chapter 7 Wiring Method Chapter 8 Memory Address on the ME-NET Chapter 9 Description for Data Link Operation Chapter 10 Description for Computer Link Operation Chapter 11 Setting of Switches and Parameters Chapter 12 Errors and Countermeasures Chapter 13 Replacement of the JW-21MN Cha
Table of contents Chapter 1: Features and Functions .......................................................................... 1-1 Chapter 2: Safety Precautions ........................................................................... 2-1 to 3 2-1 Installation .................................................................................................................................... 2-1 2-2 Wiring .....................................................................................................
Chapter 10: Description for Computer Link Operation ............................... 10-1 to 14 10-1 Computer link function ............................................................................................................. 10-1 [1] Basic commands ...................................................................................................................... 10-1 [2] Optional commands .............................................................................................................
12-3 Storage of error code ............................................................................................................... 12-6 Chapter 13: Replacement of the JW-21MN ............................................................ 13-1 Chapter 14: Support Tools ............................................................................... 14-1 to 2 Chapter 15: Specifications ............................................................................... 15-1 to 3 15-1 General specifications .
Chapter 1: Features and Functions JW-21MN is a ME-NET module for JW20/JW20H/JW30H. Using this module, you can construct an MENET combining various FA equipment such as personal computer and robot. Using this module, you can easily transmit and receive ON/OFF signals and data with devices that have a network module which is compatible with the ME-NET specifications. [When you want to install a JW-21MN in the JW30H, make sure to select one that is compatible with the JW30H.
Chapter 2: Safety Precautions 2-1 Installation Do not install or store the JW-21MN in the following conditions. - Direct sunlight - Ambient temperature exceeding the range of 0 to 55 ˚C (Storage temperature : -20 to 70 ˚C) - The relative humidity exceeding the range of 35 to 90%. - Sudden temperature changes which may cause condensation.
Communication cables should be laid from the master station to the slave station one by one. Multiple wiring from one point or wiring without terminators may cause communication errors. Joint using a connector 2 Arrange total cable length within 1 km. Arrange branch cable line from a trunk within 400 mm. Prior to any electric welding around the JW-21MN, take out the coaxial cable from the JW-21MN.
2-3 Treatment For ventilation, holes are provided in the cabinet to prevent a temperature rise. Do not block the ventilation holes. Good ventilation is necessary. Never allow a liquid such as water and chemical solution and a metallic object like a copper wire inside the JW-21MN to avoid a possible hazard. Otherwise, it may be a cause of machine trouble.
Chapter 3: System Configuration - An example of system configuration using the JW-21MN as a master station Robot Master station 00(8) JW20 JW20H JW-21MN JW30H Slave station 01(8) JW-21MN Slave station 03(8) Personal computer Slave station 77(8) Slave station 02(8) Robot control section Programmable controller ME-NET module ME-NET module ME-NET module ME-NET (64 stations max., 1 km max.
Chapter 4: Name and Function of Each Part Module retention screw (For fixing on a rack panel) Ventilation hole (Prevent temperature rise inside) 30Hn mark Indication lamp (See page 12-1) (Applied to JW30H) Module number switch (UNIT NO.) (See page 11-2) 4 Rating plate Station number switch (STA NO.
Chapter 5: Installation Installation procedure Turn "OFF" the power supply to the JW20/JW20H/JW30H. Set the mode switch, the termination resistance switch, and the shield ground switch on the rear side of the JW-21MN. (See page 11-2 to 11-4 for settings) (Rear view of the JW-21MN) 5 Applicable screwdriver Mode switch Termination resistance switch MODE ON LT OFF ON LG OFF 2 to 3mm Shield ground switch 0.
Chapter 6: Processing of Cables Make sure to use the qualified products shown below for cables and connectors. Cable and connector installation and changes must be performed only by specialists approved by the ME-NET bureau. Name Cable Model High frequency coaxial cable Crimping tools Stripper for high frequency coaxial cable ME-5C-2V ME-42H Dice: 67-42H Mitsubishi Cable Industries,. Ltd. Fujikura Cable,. Ltd. Furukawa Denko Corporation Chugoku Cable,. Ltd. Shinagawa Cable,. Ltd.
6-1 Processing cable end Applicable cable High frequency coaxial cable: ME-5C-2V Required tools Stripper for high frequency coaxial cable: CST-TM Processing procedure Move the cam wheel of the stripper (amber colored ring) back and forth and the cable holder moves back and forth accordingly. Confirm this movement of the stripper first. To hold the stripper, put your forefinger through the hole and move the cam while pushing back and forth with your thumb.
Internal conductor (annealed copper single wire) Insulator Coating External conductor (semi-transparent) (black) (meshed annealed copper wire) From the previous page Put a coaxial cable while remaining approximately 10 mm into the cable stripper and securely tighten the cable with the middle finger, ring finger, and little finger of your left hand in order to hold stable during turning the stripper.
From the previous page We recommend that in order to keep the adjusted position of the adjustment screws, after completion of adjustment for the coaxial cable and the screw holder, write the screw position etc. on a sticker and adhere it to the adjustment screws. K KE AD DA AE AD A FS KA E CA A DA AD FS FG HH G 6 Blade cassette Hold up the upper section of the screw holder with a minus driver, and open the screw holder.
6-2 Connector crimping procedure Connector parts Required tools: Hand-held crimping tool Model : ME-42H Dice No. : 67-42H Crimping width : 10 mm Sleeve Contact Shell Connector: ME-GP-01 Processing procedure Put through a sleeve to an end-processed high frequency coaxial cable. A B A:10±0.5mm B: 4±0.5mm Sleeve Insert a contact into the internal conductor and crimp. Internal conductor Contact Fixing frame Crimping dice TT- 237 1. 9.
From the previous page Slightly widen the external conductor of the coaxial cable, which is crimped to a contact on the internal conductor, in order to smoothly enter the shell inside the external conductor. Press in the external conductor end of the coaxial cable to just before the crimping part of the shell and put the sleeve into the crimping section. Then press in the coaxial cable until a “click” sound can be heard. Confirm that the contact end point touches your finger cushion.
Chapter 7: Wiring Method 7-1 Cable trunk and branch lines On the illustration of the cable wiring below, a bold line means a trunk and the thin lines branched from the trunk with a "T" shape are called branch lines. Branch line 400mm max. Trunk cable The length of branch lines branched from the trunk should be within 400 mm. 7 400mm Branch line Trunk cable Total cable length should be within 1 km. 7-2 Relaying of trunk cables To relay trunk cables, use the straight joint (ME-JJ-01).
7-3 Cable wiring procedure in control panel (1) Fixing of the cable In order not to put any force on the cable and the JW-21MN, fasten the cable to an line nearby input of a control panel or a "T" branch point to the JW21MN using saddles etc. JW-21MN Saddle Saddle (2) Extra length of cable Provide an extra length of the cable of 2 to 3 m inside a control panel for easier processing of the cable end and easier wiring when changing module positions.
(6) Bending radius of the signal cable should be less than 45 mm (outside). R4 5 or la rg er - Specification of the cable manufacturer is that bending radius should be 6x of the cable finish outside diameter (approx. 7.5 mm). (7) When you install morethan one module of the JW-21MN into one programmable controller, we recommend to put identification tag on each dable. 7 (8) Before transport or store the JW-21MN, put a protection cap on the connector of the JW-21MN.
7-4 Waterproof and insulation processing of connectors In order to prevent water intrusion into the "T" branch connectors and the straight connectors, we recommend to wind a self-adhesive tape and provide waterproof processing for them. For insulation purposes, cover these connectors with jackets. (1) "T" branch connector To wind a self-adhesive tape, cut the tape at about 10 cm each and start winding from position Start winding cut tapes from and as well.
7-5 Wiring of cables at outside control panels Do not bundle the coaxial cable (the trunk and branch lines) together with power cables, and separate from power cables at least by 100 mm. Do not put the coaxial cable into a power line wired duct. The best way is to put the communication line in an independent duct. Be careful that the coaxial cable does not receive any load by laying under a heavy weight such as other cables.
7-7 Wiring method for adding a communication station (1) Branching method When branching a line for an additional station, be sure to branch from the trunk using a T connector. Never branch from a branch line.
(3) Notes When adding a communication station, follow the items below. No. 1 2 3 4 5 6 Item Branch from the trunk cable. Don’t use the same station number twice. Check the termination resistance switch. Provide extra length for the expansion cable. Do not exceed the 1 km limit for total length of the cable. Change the layout drawing for installation. Reason Another branch line from a branch line may not give appropriate communication by reflection wave.
Chapter 8: Memory Address on the ME-NET The ME-NET employs a system for addressing individual memory banks in all of the connected equipment by allocating address throughout the ME-NET. Therefore, the top address in any link area which will contain in the data link parameters and memory addresses used for computer link instructions must be a valid memory address in the ME-NET. The relationship between memory addresses in Sharp PCs (JW20/JW20H/JW30H) and those on the ME-NET are shown below.
(2) Memory address map (against JW30H) JW30H address Relay TRM/CNT contact point ME-NET address Byte address(8) 1 address = 1 point Byte address(8) 1 address = 8 points File address(8) 1 address = 8 point Byte unit: Hexadecimal Byte unit: Octal 00000 to 15777 コ 0000 to コ 1577 000000 to 001577 0000 to 037F 000000 to 001577 001600 to 001777 0380 to 03FF 001600 to 001777 b0000 to b1777 002000 to 003777 0400 to 07FF 002000 to 003777 09000 to 09777 004000 to 004777 0800 to 09FF 004000 to 0
8-2 Memory addresses for computer links - Data memory byte addresses in the computer link must be entered the same way a data link address is entered. - The relay numbers and TMR/CNT numbers are the same for the ME-NET. However the TMR/CNT contact points correspond to the even addresses from 16000 to 17777(8). - Program addresses correspond to addresses of file (SEG)8. For details about the detailed addresses to use on the host computer, see the instruction manual for the host computer.
(2) Memory address map (against JW30H) Relay Extension relay TMR/CNT contact points Relay Extension relay TMR/CNT current value ME-NET address (8) Capacity 00000 to 15777 20000 to 75777 T-C0000 to T-C0777 T-C1000 to T-C1777 コ 0000 to コ 1577 コ 2000 to コ 7577 SEG0 00000.0 to 1577.7 SEG0 30000.0 to 35577.7 SEG0 01600.0 to 01777.7 SEG0 35600.0 to 35777.
Chapter 9: Description for Data Link Operation The data link function is used to send and receive ON/OFF signals (relay link) and data (register link) between modules by assigning one module from PCs or FA devices as the master station and other units as slave stations in the satellite net system. Up to 64 sets of PCs and FA devices can be connected in the satellite net. Each station sends data in its sending area cyclically and stores data received from other stations in its receiving area.
(2) Register link Mainly used for sending and receiving numerical data. [Example] In the case of sending 1 byte data from a master station and slave station 01 and 02.
9-2 Required transmission time and communication delay time [1] Required transmission time This is the time required for the master station to complete communication with all stations, and is determined by the number of connected stations with and the number of data items to transmit. N + 136 × P + 2.5 × P + α + 16 (ms) 1250 N : Total number of link points (value to be calculated by relay link bytes and register link bytes 8 points).
[2] Communication delay time The communication data on the ME-NET may have the delay shown below. PC00 PC00 ON I/O PC01 PC01 1 2 PC00 3 JW-21MN 4 Operation cycle (Communication) JW-21MN 5 PC01 6 I/O 7 ON 9 Delay of input module Time required for PC to detect input state (one operation cycle max.) Operation time of sending PC (one operation cycle) Time to complete sending of operation result (one communication cycle max.
[3] Data transmission between master PC and slave PC Providing synchronous transfer gives positive data communication. [An example of synchronized transfer by OUT instruction] Master station (PC00) Slave station (PC01) コ0200 コ0200 コ0203 コ0203 : Send : Receive Program in master station 00000 F-44 02030 Program in slave station 02000 02000 02000 02030 02000 - 00000 is turned "ON" at the master station side.(OUT 02000 is a self-holding circuit.
9-3 Expansion of network The JW-21MN can transmit data between 64 stations at maximum. If more than 64 stations are required for data link, you can add communication stations with the procedure below. [1] Multiple installation of the JW-21MN Mounting more than one JW-21MN on the basic rack panel of the JW20/JW20H/JW30H can increase the number of stations.
[2] Hierarchical link When 2 sets of JW-21MN are mounted on the basic rack panel of the JW20/JW20H/JW30H, hierarchical link communication is possible and can increase the number of stations.
Chapter: 10 Description for Computer Link Operation When connected to a host computer with a network module that is compatible with the ME-NET specifications, the JW-21MN can transfer data. 10-1 Computer link function The host computer communicates with each station number one by one. On the computer link, the host computer can communicate with any required station regardless of whether it is the master or slave station.
10-2 Basic commands Meaning and available memory address ranges of each command are shown in the table below - Numeric values of each command are command numbers specified by the ME-NET. - Write mode assignment shows write enabled/disabled to the PC memory. (See command No. F9(H).
10-3 Optional commands The JW-21MN optional commands are any commands not specified in the ME-NET specifications. These are commands specific to the JW-21MN. The host computer may use these optional commands for communication between JW-21MNs and PCs (JW20/JW20H/JW30H) with a JW-21MN installed. The table below shows optional commands (1) to (19) for the JW-21MN.
[1] Read free memory size Read free memory size. [Write mode assignment]: None [Communication format] Command "+" "C" "L" Response "+" ACK "A" CMD SUB ATTR "L" "A" CMD SUB "C" Symbol Data CMD 43(H) Function code SUB 4D(H) Sub code 03(H) Program memory capacity: 3.5 k words 07(H) Program memory capacity: 7.5 k words 07(H) Program memory capacity: 15.5 k words 07(H) Program memory capacity: 31.5 k words M ATTR MODE Details (Symbols other than the left: See page 10-3.) Ex.
[3] Reading PC mode Read PC's mode. [Write mode assignment]: None [Communication format] Command "+" "C" "L" "+" Response Symbol ACK Data "C" CMD SUB ATTR "L" "A" CMD SUB ATTR MODE Details CMD 43(H) Function code SUB 4E(H) Sub code 00(H) Monitor code 02(H) Change mode 03(H) Program mode MODE "A" (Symbols other than the left: See page 10-3.) [Ex.] When the PC reads program mode (Data in the cells are hexadecimal notation).
[5] Reading system memory Read the specified number of bytes of data from the specified address in system memory.
[7] Reading date Read the year, month, date, and day of week. However, when JW-21CU or JW-31CUH/H1 is used as PC, they do not have clock function and the reading will be meaningless.
[9] Reading time Read out time (hour, minute, second) of clock. However, when JW-21CU or JW-31CUH/H1 is used as PC, these PC do not have clock function and the read out data will be unsettled.
[11] Correct clock time Correct the clock setting. However, when a JW-21CU or JW-31CUH/H1 is used as PC, they do not have clock function and the reading will be meaningless.
[13] Read the optional parameters Read the parameter data for option module (other than JW-21MN) from the control module. [Write mode assignment]: None [Communication format] Command "+" "C" "L" "A" CMD SUB ATTR UNO PAADR N Response "+" ACK "C" "L" "A" CMD SUB ATTR UNO PAADR Symbol Data CMD 42(H) Function code SUB 02(H) Sub code UNO 00 to 07(H) PAADR 000 to 077(8) N 01 to 40(H) D1 to DN N D1 DN Details (Symbols other than the left: See page 10-3.) Set value for the module No.
[15] Read the special I/O parameters Read out parameter data of special I/O modules (other than JW-21MN) from the control module. [Write mode assignment]: None [Communication format] Command "+" "C" "L" "A" CMD SUB ATTR UNO PAADR N Response "+" ACK "C" "L" "A" CMD Symbol Data CMD 42(H) Function code SUB 03(H) Sub code SUB ATTR UNO PAADR N D1 DN Details 00 to 07(H) When connected to a JW20/JW20H, set the value for the module No.
[17] Set the secret function: JW30H only Enables the secret function, or deletes previously registered passwords. [Write mode assignment] - When command S = 01(H), none. - When command S = 0F(H), 2 (and when the PC is stopped by using the "PC operation stop F8(H) command.
[19] Check the secret function: JW30H only Enables/disables the secret function. [Write mode assignment]: None [Communication format] Command "+" "C" "L" "A" Response "+" ACK "C" CMD SUB ATTR "L" "A" CMD Symbol Data CMD 46(H) Function code SUB FD(H) Sub code 00(H) Disable the secret function 01(H) Enable the secret function S SUB ATTR S Details (Symbols other than the left: See page 10-3.) [Ex.
[20] Response on error When a station that has received data encounters an error while processing data after receiving an optional command from the host computer, it will send a response as follows. Response ACK "C" "L" "A" CMD ERR ACK data ERR data 01(H) None Command data format is not correct. 06(H) None PC is not stopped operation. 07(H) None Write data is not properly done. 0F(H) None Memory access time out. 10(H) None Write mode is not compatible.
Chapter 11: Setting of Switches and Parameter 11-1 Operation procedure Start Set switches of the JW-21MN Install the JW-21MN ---------- See pages 11-2 to 11-4. ---------- See page 5-1. Turn "ON" the power of the slave stations Set parameter of slave stations ---------- See page 11-22. Turn "ON" the power of the master station 11 Set parameter of master station ---------- See page 11-5. End Remarks - Make sure to turn "OFF" the power of the PC prior to setting the module No.
11-2 Switch setting of master station and slave station Prior to using the JW-21MN, set the following switches. [1] Mode switch (MODE) Set whether the JW-21MN is used as a master station or a slave station as well as the data link type (standard function or save memory function).
(3) Station number switch (STA NO.) Make sure to set the master station number to "00." For slave stations, set from "01" to "77" in octagonal sequence. - Maximum amount of slave stations to be connected are 63. As the station number should be assigned by octagonal figures, setting of the following values causes errors and the JW-21MN cannot communicate. 08, 09, 18, 19, 28, 29, 38, 39, 48, 49, 58, 59, 68, 69, and 78 to 99. - Be careful that there is no doubly allocated number and no number has been skipped.
(5) Shield ground switch (LG) For communication lines, use a coaxial cable. As coaxial cable is an unbalanced circuit, ground its shield by turning "ON" the shield ground switch.
11-3 Setting contents of master station parameters [1] Setting contents When the JW-21MN is used as a master station, set the following items for parameters. When the JW-21MN is used as a slave station, setting contents of the parameter address 004004 to 004377(8) and 004404 to 004777(8) may vary with the data link setting condition as a slave station (standard function/save memory function). For details of the parameter memory, see pages 16-8 to 16-12.
* Corresponding Set item Flag area top address e (communication and PC operation status monitor flag) - Start/stop operation of the r JW-21MN - Write to the JW21MN EEPROM. - to Parameter address(8) Initial value(H) 007764 E0 007765 symbols on pages 11-7 to 11-9 Details (set range) * 01 Set range: See page 11-11 to File address lower digits 11-12.
[2] Communication area map (1) In case that setting data link (the standard function) when the master station and all slave stations are JW-21MN's.
Register link area (Within a total of 2048 bytes) Relay link area (Within a total of 256 bytes) (2) In case that setting the data link (save memory function) when the master station and all slave stations are JW-21MN's. Memory addresses inside control module of slave station continue in order of receiving and sending.
- Set the receiving area for save memory function within the range of the link area. 0 £ a1 £ Total number of bytes of relay link area -h1 0 £ an £ Total number of bytes of relay link area -hn 0 £ b1 £ Total number of bytes of register link area -i1 0 £ bn £ Total number of bytes of register link area -in - Number of offset bytes can be set exceeding the number of sending bytes of the master station.
[Example for setting] The master station and slave station 01 and 02 are JW-21MN. It shows example for setting that slave station 01 is data link (standard function) and slave station 02 is data link (save memory function with 30H mark).
[3] Setting range of relay link area, register link area, and flag area For setting the top address of the master stations relay link, register link, and flag area, use the file address(8) allocated throughout the memory area and set the number of sending bytes of the relay link and register link area within the setting range shown below. Flag areas are allocated by 24 bytes from each top address.
(2) When master station PC is JW30H - When slave stations are JW-21MN and set to data link (the save memory function) : - When master and slave stations are JW-21MN and set to data link (the standard function) : コ0000 000000 Byte address File address (8) Byte address コ0000 000000 001000 b1777 09000 39777 49000 Register コ1500 99777 E0000 Register 003777 004000 004777 005000 005777 006000 09000 Module No. 0 Module No. 1 Module No.
[4] Setting procedure Set parameters of the master station following the procedure below.
Indications in [ ] of each item mean as follows: (Example) Stop operation of data link [HEX (hexadecimal), byte] This means to set "stop operation" by hexadecimal and byte unit. "Run" the slave station PC Turn "ON" the power of the master station PC and connect support tools Connect a support tool with the JW-21MN. JW-14PG/13PG/12PG JW-50SP JW-50PG, Z-100LP2S - For operation of each support tool, see the instruction manual attached.
From the previous page Set top address of the relay link area on the master station [OCT (octal), word] Set file address(8) to parameter address 004000 to 004001(8). - In case of setting コ0210 (file address 000210(8)) (Example for page 11-10) 004000(8) 004001(8) 0 0 0 2 1 0 (8) Screen display of JW-14PG (Word display) After converting to octal, write the data 000210.
From the previous page Write 000200 (8) in parameter addresses 004004 to 004005(8). (Word display) Convert to octal figures Slave station 01 Write 000(8) (=00(H)) in parameter address 004006(8). Write 80(H) (the top address is not same as the master station) in parameter address 004007(8). Convert to hexadecimal figures Write 00004(D) (offset 4) in parameter addresses 004010 to 004011(8). (Word display) Slave station 02 Write 00(H) in parameter address 004012(8).
From the previous page Set top address of register link area on slave station 01 to 77(8) (at standard function)/number of offset bytes (at save memory function) Set in parameter addresses 004404 to 004777(8). These top addresses should not overlap the resister link area, flag area, or any area used by other option module.
From the previous page Set the number of sending bytes of the slave station (01 to 77) relay link [DCM (decimal), word] Set the number of sending bytes in decimal on the parameter addresses 005002 to 005177(8). (set in each station, 2 bytes for each station). These top addresses should not overlap the resister link area, or the flag area, or exceed the setting range (0 to 256 bytes for each station, 256 bytes for all stations in total).
From the previous page Set connection status of slave station [bit pattern, byte] Set "connected slave station as 01 and 02, output error code" in paramenter address 007750(8). 007750(8) 7 6 5 4 3 2 1 0 0 0 0 0 0 1 1 1 Display the contents of parameter address 007750(8) Turn "ON" bit 0 (output error code) Turn "ON" bits 1 and 2 (connects slave station 01 and 02) Screen display of JW-14PG 07746 □□□□□□□□ 07747 □□□□□□□□ I PARAM.
From the previous page File address: OCT (octal), word File number/flag: HEX (hexadecimal), byte Set top address of flag area Set the top address of the flag area (24 bytes) in order to monitor the communication condition and PC operation condition on the parameter address 007764 to 007767(8). Flag area uses 24 bytes regardless number of connecting stations.
From the previous page Writing to the EEPROM of the JW-21MN, start operation [HEX (hexadecimal), byte] Write "81(H)" into parameter address 007777(8) and write the set parameter contents into the EEPROM of the JW-21MN. Then start the JW-21MN. After starting operation, the setting value changes to "01(H).
11-4 Setting slave station parameters (common for all slave stations) When the JW-21MN is used as a slave station, set the following items for parameters.
[2] Setting range of flag area Flag areas are allocated by 24 bytes from each top address. For setting the top address of flag area, use the file address(8) allocated throughout the memory area and set within the setting range shown below.
[3] Setting procedure When not using save memory function [ ] : See page in chapter 11 Turn "ON" the power of slave station PC [ 25 ] Connect support tools [ 25 ] Stop PC operation [ 25 ] Stop operation of data link (007777(8) =00(H)) [ 25 ] ① V2 Set number of receiving bytes of relay link in save memory function [ 26 ] ② V2 Set number of receiving bytes of register link in save memory function [ 26 ] ③ V2 ④ ⑤ Whether the station number information should be output or not Set top addr
Indications in [ ] of each item mean as follows: (Example) Stop operation of data link [HEX (hexadecimal), byte] This means to set "stop operation" by hexadecimal and byte unit. Turn "ON" the power of slave station PC Connect support tools (JW-14JG) Connect a support tool with the JW-21MN. JW-14PG/13PG/12PG JW-50SP JW-50PG, Z-100LP2S - For operation of each support tool, see the instruction manual attached. The following describes an example of JW-14PG's key operation.
From the previous page "Only when using save memory function" V2 Set the number of sending bytes of the relay link in save memory function [DCM (decimal), word] Set the number of sending bytes in decimal on the parameter address 007720 to 007721(8). Lower Upper 007200(8) 007721(8) - In case of setting 4 bytes (Example for page 11-10) Display the contents of parameter addresses 007720 to 007721(8) Write 00004(D) after converting to decimal Screen display of JW-14PG 07714 07716 I PARAM.
From the previous page File address: OCT (octal), word File number/flag: HEX (hexadecimal), byte Set top address of flag area Set the top address of the flag area (24 bytes) in order to monitor the communication condition and PC operation condition on the parameter address 007764 to 007767(8). Flag area uses 24 bytes regardless number of connecting stations.
From the previous page Writing to the EEPROM of the JW-21MN, start operation [HEX (hexadecimal), byte] Write "81(H)" into parameter address 007777(8) and write the set parameter contents into the EEPROM of the JW-21MN. Then start the JW-21MN. After starting operation, the setting value changes to "01(H).
Chapter 12: Errors and Countermeasures The operating condition of the JW-21MN can be monitored using its indication lamps, flags, and the system memory of a PC. ME-NET 12-1 Indication lamps LED name COMM Details CM Lights during data link operation SD Lights while sending data RD Lights while receiving data CD Lights when detecting carrier LT Lights when turning “ON” the termination resistance T Lights during testing (TEST) COM.
12-2 Flag Flag area is 24 bytes from the "flag top address" set in the master station/slave station parameters.
[2] In the case of a master station (1) Communication monitor flag This flag is used to monitor the communication condition with other stations. Non-connected station keeps this flag as "OFF." Flag Own station flag (master station) Flag Flag operation Condition for flag operation When the parameter address 007777(8) of the master station is set to "01(H)," and the master station is operating normally. ON When the parameter address 007777(8) of the master station is set to "00(H).
[3] In the case of slave station 01 to 77(8) (1) Communication monitor flag This flag is used to monitor the communication condition with other stations. Non-connected station keeps this flag as "OFF." Flag Condition for flag operation When the parameter address 007777(8) of each slave station is set to "01(H)," and at communicating with a master station normally. Own station When the parameter address 007777(8) of each slave station is "00(H).
[4] Monitor operation condition by each station PC By creating a program having the flags shown below in each station's PC, the JW-21MN can monitor the operation condition of each station’s PC. [Ex.
12-3 Storage of error code When an error occurs in the JW-21MN, it stores the occurred error’s code to system memory #160, #170 and error history storage register of each station's PC.
(1) System memory #170 to 177 (option module error code) The error code stored in the system memory #170 is shifted to #170 to #177 one after the other as new errors occur. Thus, the system memory can store up to 8 errors. When the PC is operating by RAM, these error codes do not disappear even after turning OFF the power. The contents of system memory #170 to #177 are kept storing after the JW-21MN recovers from the error.
(4) Error history When the JW-21MN has errors, it stores them in an error history register. The storage area is specified using the module No. switch setting value. Error history storage register Module No.
Chapter 13: Replacement of the JW-21MN When you want to change the JW-21MN due to an operation fault (lighting UNT.E lamp) etc., follow the procedures below. Make sure to store the set parameters onto a floppy diskette using a support tools.
Chapter 14: Support Tools The following support tools are available to record (store), and load the contents of the parameter memory. (Make sure to save the set parameters onto a floppy diskette.) Model name Applicable floppy diskettes Ladder software (JW-92SP, JW-50SP) 3.5-inch 2DD/2HD, 5-inch 2DD/2HD Multipurpose programmer (JW-50PG) 3.5-inch 2DD Ladder processor II (Z-100LP2S) 3.
(1) Load to the personal computer Load the contents of the floppy diskette into the memory of the personal computer. Select "FD TRANS." Select "Load." Select a file name. Press the "Enter" key. JW-50SP JW-21MN Start loading into the personal computer. (2) Stop operation of the JW-21MN After stopping operation, load the memory contents of the personal computer into the JW-21MN. Select "PC TRANS." Select "Write." Select "DL M. stn. PARAM." or "DL S. stn. PARAM.
Chapter 15: Specifications 15-1 General specifications Item Specification New satellite JW20/JW20H (JW-21CU/22CU) Applicable PC New satellite JW30H (JW-31CUH/32CUH/33CUH, JW-31CUH1/32CUH1/33CUH1/33CUH2/33CUH3) Installing slot Basic rack panel of JW20/JW20H/JW30H Storage temperature −20 to +70℃ Ambient temperature 0 to +55℃ Ambient humidity 35 to 90%RH (without condensation) Vibration resistance JIS-C-0911 equivalent (X, Y, Z, 2 hours each) Shock resistance JIS-C-0912 equivalent Internal power consumption
15-3 Data link specifications Both standard function and save memory function are available. Select by the mode switch on the JW-21MN. (1) Standard function Specifications Item Amount of connectable stations Link area Relay link Register link Flag area Total number of links 64 stations max.
15-4 Computer link specifications Specifications Item Link station Communication data size Communication control Control functions 64 stations max.
Chapter 16: Appendix 16-1 Maintenance and check Check wiring, installation, and switch settings. System configuration ( ) ( ) ( ) ( ) ( ) Check item Communication cable Not parallel with or proximate to high voltage lines or strong power lines. Branch lines (drop cable) are within 400 mm. Total length is less than 1 km. No damage or breaks in cables. Connectors are securely assembled. Connectors are securely connected and locked.
16-2 Recovery method at communication errors (1) Check flow chart Occurrence of error Connection status of cable/connector are normal. NO See "Check cable/connector" on next page. YES See "During initial communication" on page 16-5. YES First communication? NO Does the error occur continuously? NO See "When the communication error occurs instantaneously " on page 16-7. YES See "When the communication error occurs continuously" on page 16- 7.
(2) Check cable/connector As errors on the junction from the main cable to the drop cable or the contact failure on the connecting point of each station or errors of the master module are assumed, check with the following procedure. UNT. E lamp turns ON YES Exchange master module NO Monitor individual communication flag in support tool.
- If the bus cable between the slave station 05(8) and 06(8) is disconnected in the following system. 03(8) 02(8) 01(8) 04(8) Master station 05(8) B C D Disconnection A 06(8) 07(8) State of an individual communication flag D7 6 5 4 3 2 1 D0 OFF Unstable OFF Remove the connector on point A, and turn ON the termination resistance of the master station. As the communication possible stations 03(8), 02(8), 01(8), and 04(8) are normal, the state of communication monitoring flag is as follows.
(3) During initial communication (startup of the system) Lighting error code 6F(H) - When the master station indicates error code 6F(H) and the COMM lamp is OFF. The cause may be a parameter setting error of the master station. Check the master station parameters below.
When the COMM lamp of the master station is OFF (SD, RD, and CD are flickering). Check the following master station's parameters. Parameter address(8) Contents Setting value 004002 Function (relay/register link) 01(H) 007777 Start/stop operation of the JW-21MN 01(H) Other cases - Check the switches of the JW-21MN (see check item) Check optional cable of PC (The JW-21MN does not operate normally without an optional cable.
(4) When the communication error occurs instantaneously. Cause may be: - Noise on the communication line. - Fault of a communication module. - Fault of a communication cable. Check the error's timing. When the error occurs synchronous with a peripheral industrial robot's operation, noise to the communication line may be a cause. Consider arrangement of the wiring route. Identify the error station. When the error occurs at only the specific station, the cause may be the station or nearby.
16-3 Table of parameter memory (1) Master station The set contents of the parameter addresses 004004 to 004377(8) and 004404 to 004777(8) shown below are in the case that a JW-21MN is used for a slave station.
(2 / 5) Address(8) 004400 004401 004402 004403 004404 to 004407 Setting method (value, example) Set contents Top address of register link area in the master station (Octal, word) (Hexadecimal, byte) When 09000(8), set to 004000(8) (Set by file address) When file number is 1 -> 01(H) 00(H) - When slave station 01(8) is set to data link (the standard function), top address of the register link area on slave station 01(8) are as shown at right.
(3 / 5) Address(8) 005000 005001 005002 005003 Set contents Setting method (value, example) Number of sending bytes of master station relay link area (Decimal, word) Number of sending bytes of slave station 01(8) relay link area (Decimal, word) Address(8) Address(8) Set contents Number of sending bytes of slave station 02(8) relay link area (same as 005002 to 005003).
(4 / 5) Address(8) 005200 005201 005202 005203 Set contents Setting method (value, example) Number of sending bytes of master station register link area (Decimal, word) Number of sending bytes of slave station 01(8) register link area (Decimal, word) When 64 bytes, set to 00064(D) Address(8) Set contents Address(8) 005204 to 005205 Number of sending bytes of slave station 02(8) register link area (same as 005202 to 005203).
(5 / 5) Address(8) Set contents Setting method (value, example) Bit address 007750 to 007757 Connection condition of slave station - Turn ON the corresponding bit of connected station number (01 to 77(8)) from the list at right. - 00(8) of master station (0 bit of address 000750) At ON: Output error code At OFF: Do not output error code.
16-4 Special functions unique to the JW-21MN The functions below are not covered by the ME-NET specifications. They can only be used with PCs which are equipped with a JW-21MN, ME-NET module JW-20MN or ZW-20CM2. (1) Remote programming and remote monitor This paragraph describes the operation procedure of any other station's PC which is connected on the ME-NET. The following support tools are available: Hand-held programmer ..................... JW-14PG/13PG/12PG Multipurpose programmer .................
Function < Standard network connection > n— 2 n— 1 Support tool n n+ 1 n+ 2 ME-NET Writing data (change program) during operation of the PC is not available for hazard prevention reasons. Stop operation of the PC prior to writing data. The operations below using a peripheral device, that is connected to a "n" station, is possible.
- Network setting Select whether the target station for remote programming or remote monitor is on the standard network connection or on the extension network connection. In the case below, 10 to 12(8) are standard network connections. 01 to 03(8) are extension network connections. (JW-50PG) 12(8) (Junction station) 10(8) 00(8) 11(8) 01(8) Target station 02(8) 03(8) ME-NET 0 1 Slot number 2 3 ME-NET Set "standard" in network configuration.
(2) Parameter setting by remote function This paragraph describes how to set the parameters of other stations' network module (JW-21MN/ JW-20MN) connected on the ME-NET. This is only available when the target station is within the standard network connection. Usable support tools are JW-14PG/13PG/12PG. < An operation example using the JW-14PG > Connect the programmer to the JW-21MN on the ME-NET. Select initial mode. → Display initial mode. (JW-21MN) Assign the parameter setting remotely.
Alphabetical Index [A] Allocation of relay number ........................................................................................ 2-3 Appendix ................................................................................................................. 16-1 [B] Basic commands ............................................................................................ 10-1, 10-2 Branching method ....................................................................................................
[M] Maintenance and check .......................................................................................... 16-1 Maintenance ............................................................................................................. 2-3 Memory address for data links .................................................................................. 8-1 Memory Address on the ME-NET ............................................................................. 8-1 Mode switch ........................
Setting special I/O parameter ............................................................................... 10-11 Setting time ............................................................................................................. 10-8 Shield ground switch ............................................................................................... 11-4 Special functions unique to the JW-21MN ............................................................ 16-13 Specifications ........................