Operating Manual

Installation, assembly and commissioning for
the first time
Version 1.1 Page 37 of 92
Figure 4-1 : Requirements for the installation site, distance of the ESS from walls, top view
Figure 4-2 : Requirements for the installation site, distance of the ESS from walls, side view
The room air must not contain contaminations like suspended particles, metal dust or combustible gases. Ensure that
the air humidity does not exceed 80%.
The room temperature should be in a range from 0 °C to 25 °C, wherein 15-20 °C are optimum for a long service life.
Operate the battery storage system only in the upright position.
Ensure that the service flap at the side (NH1 fuses) is always freely accessible.
Install the battery inverter and the battery storage system near each other. Do not lay the connecting cable between
the battery and the inverter in windings. The maximum length of this cable is 2.3 m.