3.1.6 Mounting bracket
When installing the battery pack on a wall, make sure that the wall is capable of supporting the
weight of the battery pack.
To mount the battery pack on a wall, take the following steps :
1. Mark the location on the wall for the holes.
2. Drill holes for fasteners in the wall.
3. Drive the fasteners through the mounting bracket into the holes.
Recommended diameter :
10mm(0.4") Min.
Recommended length :
70mm(2.8") Min.
Recommended material :
Stainless steel (8.8T)
Recommended fastener count :
4(Area1)/2(Area2)/4(Area3)/2(Area4)
- Vertically
Recommended minimum fastener
clearance :
At least 250mm (10")
ex. Between Area 1’s last fastener and
Area 2’s first fastener
CAUTION
Make sure that the battery pack is at all times exposed to the ambient air.
The battery pack is cooled by natural convection. If the battery pack is entirely or
partially covered or shielded, it may cause the battery pack to stop operating.