Installation Manual RESU 10H SEG Type-R

3.2 Cable connection
123
1. See 3.2.1. for Power Cable specications
a) Connect the ground wire to
terminal 1.
b) Connect the negative line of the
power cable to terminal 2.
c) Connect the positive line of the
power cable to terminal 3.
123456
2. See 3.2.1. for Communication Cable
specications
Install protection cover before turning on.
At rst, connect the ground wire to
terminal 2. Then, make connections
to the other terminals one after another.
Installation
24
4.
After turning disconnect switch ON,
Turn on the circuit breaker.
3.
Connecting the battery pack to the inverter
Refer to the Installation Instructions
For the inverter to connect the power cable
And communication cable to the inverter.
Then, push the disconnect switch up
So that it is in the ON position.
Must turn off to reduce self-discharge of
battery during shipping and storage.
CAUTION
MUST follow the turn on procedure.