Specifications

Parameter list
DRIVE THE MOTOR
17
6.2 Parameter list
For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the necessary parameters to meet the load
and operational specifications. Parameter setting, change and check can be performed from the operation panel (FR-DU08).
Pr. Name
Setting
range
Initial
value
0 Torque boost 0 to 30%
6/4/3/2/1%
1 Maximum frequency 0 to 120Hz
120Hz
60Hz
2 Minimum frequency 0 to 120Hz 0Hz
3 Base frequency 0 to 590Hz
60/50Hz
4
Multi-speed setting
(high speed)
0 to 590Hz
60/50Hz
5
Multi-speed setting
(middle speed)
0 to 590Hz 30Hz
6
Multi-speed setting (low
speed)
0 to 590Hz 10Hz
7 Acceleration time 0 to 3600s
5s
15s
8 Deceleration time 0 to 3600s
5s
15s
9
Electronic thermal O/L
relay
0 to 500A
Rated
inverter
current
0 to 3600A
10
DC injection brake
operation frequency
0 to 120Hz,
9999
3Hz
11
DC injection brake
operation time
0 to 10s, 8888 0.5s
12
DC injection brake
operation voltage
0 to 30% 4/2/1%
13 Starting frequency 0 to 60Hz 0.5Hz
14 Load pattern selection 0 to 5 0
15 Jog frequency 0 to 590Hz 5Hz
16
Jog acceleration/
deceleration time
0 to 3600s 0.5s
17 MRS input selection 0, 2, 4 0
18
High speed maximum
frequency
0 to 590Hz
120Hz
60Hz
19 Base frequency voltage
0 to 1000V,
8888, 9999
9999/8888
20
Acceleration/
deceleration reference
frequency
1 to 590Hz
60/50Hz
21
Acceleration/
deceleration time
increments
0, 1 0
22
Stall prevention
operation level
(Torque limit level)
0 to 400% 150%
23
Stall prevention
operation level
compensation factor at
double speed
0 to 200%, 9999
9999
24 to
27
Multi-speed setting (4
speed to 7 speed)
0 to 590Hz,
9999
9999
28
Multi-speed input
compensation selection
0, 1 0
29
Acceleration/
deceleration pattern
selection
0 to 6 0
30
Regenerative function
selection
0 to 2, 10, 11,
20, 21,
100 to 102, 110,
111, 120, 121
0
31 Frequency jump 1A
0 to 590Hz,
9999
9999
32 Frequency jump 1B 9999
33 Frequency jump 2A 9999
34 Frequency jump 2B 9999
35 Frequency jump 3A 9999
36 Frequency jump 3B 9999
37 Speed display 0, 1 to 9998 0
41
Up-to-frequency
sensitivity
0 to 100% 10%
42
Output frequency
detection
0 to 590Hz 6Hz
43
Output frequency
detection for reverse
rotation
0 to 590Hz,
9999
9999
44
Second acceleration/
deceleration time
0 to 3600s 5s
45
Second deceleration
time
0 to 3600s,
9999
9999
46 Second torque boost 0 to 30%, 9999 9999
47
Second V/F (base
frequency)
0 to 590Hz,
9999
9999
48
Second stall prevention
operation level
0 to 400% 150%
49
Second stall prevention
operation frequency
0 to 590Hz,
9999
0Hz
50
Second output
frequency detection
0 to 590Hz 30Hz
51
Second electronic
thermal O/L relay
0 to 500A, 9999
9999
0 to 3600A,
9999
52
Operation panel main
monitor selection
0, 5 to 14,
17 to 20,
22 to 35, 38,
40 to 45,
50 to 57, 61,
62, 64, 67,
87 to 98, 100
0
54
FM/CA terminal
function selection
1 to 3, 5 to 14,
17, 18, 21, 24,
32 to 34, 50, 52,
53, 61, 62, 67,
70, 87 to 90, 92,
93, 95, 97, 98
1
55
Frequency monitoring
reference
0 to 590Hz
60/50Hz
56
Current monitoring
reference
0 to 500A
Rated
inverter
current
0 to 3600A
57 Restart coasting time
0, 0.1 to 30s,
9999
9999
58 Restart cushion time 0 to 60s 1s
59
Remote function
selection
0 to 3, 11 to 13 0
60
Energy saving control
selection
0, 4, 9 0
61 Reference current
0 to 500A, 9999
9999
0 to 3600A,
9999
62
Reference value at
acceleration
0 to 400%, 9999 9999
63
Reference value at
deceleration
0 to 400%, 9999 9999
64
Starting frequency for
elevator mode
0 to 10Hz, 9999 9999
65 Retry selection 0 to 5 0
66
Stall prevention
operation reduction
starting frequency
0 to 590Hz
60/50Hz
67
Number of retries at
fault occurrence
0 to 10, 101 to
110
0
68 Retry waiting time 0.1 to 600s 1s
69
Retry count display erase
0 0
70
Special regenerative
brake duty
0 to 100% 0%
71 Applied motor
0 to 6, 13 to 16,
20, 23, 24, 30,
33, 34, 40, 43,
44, 50, 53, 54,
70, 73, 74, 330,
333, 334, 8090,
8093, 8094,
9090, 9093,
9094
0
72
PWM frequency
selection
0 to 15
2
0 to 6, 25
73 Analog input selection 0 to 7, 10 to 17 1
74 Input filter time constant 0 to 8 1
75
Reset selection/
disconnected PU
detection/PU stop
selection
0 to 3, 14 to 17
14
0 to 3, 14 to 17,
100 to 103,
114 to 117
76
Fault code output
selection
0 to 2 0
77
Parameter write
selection
0 to 2 0
78
Reverse rotation
prevention selection
0 to 2 0
79
Operation mode
selection
0 to 4, 6, 7 0
80 Motor capacity
0.4 to 55kW,
9999
9999
0 to 3600kW,
9999
81 Number of motor poles
2, 4, 6, 8, 10,
12, 9999
9999
82 Motor excitation current
0 to 500A, 9999
9999
0 to 3600A,
9999
83 Rated motor voltage 0 to 1000V
200/400V
84 Rated motor frequency
10 to 400Hz,
9999
9999
89
Speed control gain
(Advanced magnetic
flux vector)
0 to 200%, 9999 9999
Pr. Name
Setting
range
Initial
value
90 Motor constant (R1)
0 to 50 , 9999
9999
0 to 400m ,
9999
91 Motor constant (R2)
0 to 50 , 9999
9999
0 to 400m ,
9999
92
Motor constant (L1)/d-
shaft inductance (Ld)
0 to 6000mH,
9999
9999
0 to 400mH,
9999
93
Motor constant (L2)/q-
shaft inductance (Lq)
0 to 6000mH,
9999
9999
0 to 400mH,
9999
94 Motor constant (X) 0 to 100%, 9999 9999
95
Online auto tuning
selection
0 to 2 0
96
Auto tuning setting/
status
0, 1, 11, 101 0
100 V/F1(first frequency)
0 to 590Hz,
9999
9999
101
V/F1(first frequency
voltage)
0 to 1000V 0V
102
V/F2(second
frequency)
0 to 590Hz,
9999
9999
103
V/F2(second frequency
voltage)
0 to 1000V 0V
104 V/F3(third frequency)
0 to 590Hz,
9999
9999
105
V/F3(third frequency
voltage)
0 to 1000V 0V
106 V/F4(fourth frequency)
0 to 590Hz,
9999
9999
107
V/F4(fourth frequency
voltage)
0 to 1000V 0V
108 V/F5(fifth frequency)
0 to 590Hz,
9999
9999
109
V/F5(fifth frequency
voltage)
0 to 1000V 0V
110
Third acceleration/
deceleration time
0 to 3600s,
9999
9999
111 Third deceleration time
0 to 3600s,
9999
9999
112 Third torque boost 0 to 30%, 9999 9999
113
Third V/F (base
frequency)
0 to 590Hz,
9999
9999
114
Third stall prevention
operation level
0 to 400% 150%
115
Third stall prevention
operation frequency
0 to 590Hz 0Hz
116
Third output frequency
detection
0 to 590Hz
60/50Hz
117
PU communication
station number
0 to 31 0
118
PU communication
speed
48, 96, 192, 384,
576, 768, 1152
192
119
PU communication stop
bit length / data length
0, 1, 10, 11 1
120
PU communication parity
check
0 to 2 2
121
Number of PU
communication retries
0 to 10, 9999 1
122
PU communication
check time interval
0, 0.1 to 999.8s,
9999
9999
123
PU communication
waiting time setting
0 to 150ms,
9999
9999
124
PU communication CR/
LF selection
0 to 2 1
125
Terminal 2 frequency
setting gain frequency
0 to 590Hz
60/50Hz
126
Terminal 4 frequency
setting gain frequency
0 to 590Hz
60/50Hz
127
PID control automatic
switchover frequency
0 to 590Hz,
9999
9999
128 PID action selection
0, 10, 11, 20, 21,
40 to 43, 50, 51,
60, 61, 70, 71,
80, 81, 90, 91,
100, 101, 1000,
1001, 1010,
1011, 2000,
2001, 2010, 2011
0
129 PID proportional band
0.1 to 1000%,
9999
100%
130 PID integral time
0.1 to 3600s,
9999
1s
131 PID upper limit 0 to 100%, 9999 9999
132 PID lower limit 0 to 100%, 9999 9999
Pr. Name
Setting
range
Initial
value