Specifications

26
SPECIFICATIONS
Rating
400 V class
The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
The rated output capacity indicated assumes that the output voltage is 440 V for 400 V class.
When an operation is performed with the carrier frequency set to 3 kHz or more, and the inverter output current reaches the value indicated in the parenthesis of the
rated current, the carries frequency is automatically lowered. The motor noise becomes louder accordingly.
The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter
and motor to return to or below the temperatures under 100% load.
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the maximum
point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about .
Value by the built-in brake resistor
Value for the ND rating
The rated input current indicates a value at a rated output voltage. The impedance at the power supply side (including those of the input reactor and cables) affects the
rated input current.
The power supply capacity is the value when at the rated output current. It varies by the impedance at the power supply side (including those of the input reactor and
cables).
FR-DU08: IP40 (except for the PU connector section)
For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For details, refer to the Instruction Manual (Detailed)).
The braking capability of the inverter built-in brake can be improved with a commercial brake resistor. For the details, please contact your sales representative.
Model FR-A840-[ ]
00023 00038 00052 00083 00126 00170 00250 00310 00380 00470 00620 00770 00930 01160 01800 02160 02600 03250 03610 04320 04810 05470 06100 06830
0.4K
0.75K
1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K
18.5K
22K 30K 37K 45K 55K 75K 90K 110K 132K 160K 185K 220K 250K 280K
Applicable motor
capacity (kW)
SLD 0.751.52.23.75.57.5111518.52230374555
75/
90
110132160185220250280315355
LD 0.751.52.23.75.57.5111518.522303745557590110132160185220250280315
ND (initial setting)0.40.751.52.23.75.57.5111518.522303745557590110132160185220250280
HD 0.20.40.751.52.23.75.57.5111518.522303745557590110132160185220250
Output
Rated
capacity
(kVA)
SLD 1.82.946.310131924293647597188137165198248275329367417465521
LD 1.62.73.75.88.8121822273343536581110137165198248275329367417465
ND (initial setting)1.11.934.66.99.1131824293443546684110137165198248275329367417
HD 0.61.11.934.66.99.1131824293443546684110137165198248275329367
Rated
current (A)
SLD
2.3
(2)
3.8
(3.2)
5.2
(4.4)
8.3
(7.1)
12.6
(10.7)
17
(14.5)
25
(21.3)
31
(26.4)
38
(32.3)
47
(40)
62
(52.7)
77
(65.5)
93
(79.1)
116
(98.6)
180
(153)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
547
(465)
610
(519)
683
(581)
LD
2.1
(1.8)
3.5
(3)
4.8
(4.1)
7.6
(6.5)
11.5
(9.8)
16
(13.6)
23
(
19.6)
29
(24.7)
35
(
29.8)
43
(36.6)
57
(48.5)
70
(59.5)
85
(72.3)
106
(90.1)
144
(122)
180
(153)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
547
(465)
610
(519)
ND (initial setting)
1.5
(2.3)
2.5
(3.8)
4
(6)
6
(9)
9
(13.5)
12
(18)
17
(25.5)
23
(34.5)
31
(46.5)
38
(57)
44
(66)
57
(85.5)
71
(107)
86
(129)
110
(165)
144
(216)
180
(270)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
547
(465)
HD
0.8
(2.3)
1.5
(3.8)
2.5
(6)
4
(9)
6
(13.5)
9
(18)
12
(25.5)
17
(34.5)
23
(46.5)
31
(57)
38
(66)
44
(85.5)
57
(107)
71
(129)
86
(165)
110
(216)
144
(270)
180
(153)
216
(184)
260
(221)
325
(276)
361
(307)
432
(367)
481
(409)
Overload
current rating
SLD 110% 60 s, 120% 3 s (inverse-time characteristics) at surrounding air temperature 40°C
LD 120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air temperature 50°C
ND (initial setting)150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air temperature 50°C
HD 200% 60 s, 250% 3 s (inverse-time characteristics) at surrounding air temperature 50°C
Rated voltage
Three-phase 380 to 500 V
Regenerative
braking
Brake transistorBuilt-in FR-BU2(Option)
Maximum brake torque 100% torque/2%ED
20% torque/continuous 10% torque/continuous
FR-ABR
(when the option is used)
100% torque/10%ED 100% torque/6%ED
Power supply
Rated input
AC voltage/frequency
Three-phase 380 to 500 V 50 Hz/60 Hz
Permissible AC voltage fluctuation323 to 550 V 50 Hz/60 Hz
Permissible frequency fluctuation±5%
Rated input
current (A)
SLD 3.25.47.810.916.422.531.740.348.258.476.897.6115141180216260325361432481547610683
LD 34.97.310.115.122.33138.244.953.975.189.7106130144180216260325361432481547610
ND (initial setting)2.33.76.28.312.317.422.53140.348.256.575.191108134144180216260325361432481547
HD 1.42.33.76.28.312.3 17.422.53140.348.256.575.191108110144180216260325361432481
Power supply
capacity
(kVA)
SLD 2.54.15.98.3121724313744597488107137165198248275329367417465521
LD 2.33.75.57.712172429344157688199110137165198248275329367417465
ND (initial setting)1.72.84.76.39.4131724313743576983102110137165198248275329367417
HD 1.11.72.84.76.39.413172431374357698384110137165198248275329367
Protective structure (IEC 60529)
Enclose type (IP20) Open type (IP00)
Cooling system Self-coolingForced air cooling
Approx. mass (kg) 2.82.82.83.33.36.76.78.38.315152341414352557178117117166166166