Specifications

28
On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay output has basic isolation from the inverter
internal circuit.)
Control circuit terminals on page 5 are safely isolated from the main circuit.
Environment (For the detail, refer to the Instruction Manual (Detailed).)
Wiring protection
Class T, Class J, Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.T or UL 489 Molded Case Circuit Breaker (MCCB) must
be provided.
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
Short circuit ratings
! 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 264 V Maximum.
! 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 550 V or 600 V Maximum.
During Operation In Storage During Transportation
Surrounding air temperature
LD, ND (initial setting), HD: -10 to +50°C (14 to 122°F)
SLD: -10 to +40°C (14 to 104°F)
-20 to +65°C (-4 to +149°F)-20 to +65°C (-4 to +149°F)
Ambient humidity95% RH or less95% RH or less95% RH or less
Maximum altitude2500m (8202 feet)2500m (8202 feet)10000m (32808 feet)
FR-A820-[]
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
Rated fuse voltage(V) 240V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
152030406080150175200
With power factor
improving reactor
152020305070125150200
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
151525406080110150190
FR-A820-[]
00930
(18.5K)
01250
(22K)
01540
(30K)
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage(V) 240V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
225300350400500500
With power factor
improving reactor
200250300350400500600700
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
2253003504505007009001000
FR-A840-[]
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage(V) 500V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
61015203040708090110150175
With power factor
improving reactor
61010152535607090100125150
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
151515203040607090100150175
FR-A840-[]
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage(V) 500V or more
Fuse Maximum
allowable rating
(A)
Without power
factor improving
reactor
200250300
With power factor
improving reactor
1752002503003504005006007008009001000
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)
2252504504505006008009001000120012001200