NUJB395

SIM02E-001
4
INSTALLATION INSTRUCTIONS -PHOTOVOLTAIC MODULES-
1. INSTALLATION
The mounting method has been verified by SHARP and NOT
CERTIFIED by a third party organization. Please review the
descriptions and drawings carefully; not mounting the PV
modules according to one of these methods may void your
guaranty.
(Design load according to IEC61215 is 2,400Pa positive and
1,600Pa negative)
Mounting Using Clips: Clamping on Longer Frame (Figure2)
The PV modules can be mounted using clips (clamps) designed for PV
modules as defined in the following Figures. Note that the mounting clips
should meet the required dimensions as defined in the Figure1. Note that the
CLIP CENTER POSITION (e) is important as specified in the Figure2. The PV
module must be supported on the array system and should overlap the array
rail by at least 10mm. The array rails must support the bottom of the frames
and must be continuous piece (no breaks in the rail).
2. ELECTRICAL INSTALLATION INSTRUCTION
CABLE requirement
Conductor size: 4.0mm
2
Min.
Cable type: XLPE cable (H1Z2Z2-K cable)
Maximum DC voltage: 1.5kV
Rating temperature: -40°C to +90°C
Maximum conductor temperature:120
PV module configuration (Recommend)
# Maximum series configuration: please refer to Table-1
(This value is calculated under the condition of Voc at -40 °C.)
# Maximum parallel configuration: (Parallel connection of each
string shall be conducted with following two options. Any other
parallel connections are prohibited.)
a) Case of using the diodes; 1 diode per maximum 2 parallel
strings (Connect a diode or more in series for every string or
every 2 parallel strings for protection of PV module from reverse
current over load.)
b) Case of using the fuses; 1 fuse per every string (Connect a
fuse for every single string for protection of PV module from
reverse current over load.)
CONNECTOR requirement
The PV module shall be mated to the same connectors;
No connectors shall be cut from the electrical cable.
Type: C1
Brand: Solargiga Energy Holdings Limited
3. WARNING
Keep all PV MODULES and
electriacal CONNECTORS clean &
dry before installation.
4. Disposal
Dispose PV modules properly. For
Information about the proper
disposal, contact your local
recycling site.
ELECTRICAL OUTPUT AND THERMAL CHARACTERISTICS
Rated electrical characteristics are within ±10 percent of the indicated values of Voc, Isc and +5/-0 percent of Pmax (power
measurement tolerance: ± 3%), under STC (standard test conditions) (irradiance of 1000W/m
2
, AM 1.5 spectrum, and a cell
temperature of 25°C (77°F)).
T able-1. Electrical characteristics (at S T C )
Model
name
Max imum
Power
(Pmax )
Tolerance
Open-Curcuit
Voltage
(Voc)
Short-Circuit
Current
(Isc)
Voltage at point
of max. Power
(Vmpp)
Current at point
of max . Power
(Impp)
Max imum
system voltage
Over-Current
Protection
Class for protection
against elecrical
shock
Max imum series
configuration(*)
NU-JB395 395W +5%/-0% 49.45V 10.35A 41.07V 9.62A 1,500V 20A
25
* The maximum series number of modules depends on the local conditions. These values are calculated under the condition of Voc at -40 °C.
Under normal conditions, a PV module is likely to experience conditions that produce more current and/or voltage than reported
at Standard Test Conditions. Accordingly, the values of Isc and Voc marked on this PV module should be multiplied by a factor of
1.25 when determining component voltage ratings, conductor capacities, fuse sizes and size of controls connected to the PV
module output.
The PV module has been qualified in an environmental temperature range of -40 °C to +40 °C and up to 100% relative humidity
as well as rain, and the altitude up to 2,000m in accordance with IEC61730.
Class for protection against electric shock
This PV module is classified as “Class according to
IEC61730. These PV modules are intended for installation
where geeral user access and contact to insulated live parts is
anticipated.
FIRE RATING
This PV module is rated as “Fire safety class C” according to
IEC61730-2:2004 or UL790.
Figure1. Clips (Clamps) requirement
1) Clip: Al alloy, 3 mm Min. thickness
2) Catch length (50 mm Min.)
3) Covering depth (7 mm Min. on the frame)
4) Supporting depth (10 mm Min.)
5) Frame (applicable to all frame sections)
6) Array rail
(applicable to parallel or crossed mounting)
Figure2. Clamping on longer Frame
300 mm < e < 400 mm
e
: span from PV module corner to clip center
e
e
e
e