User`s manual

10
NOTE: If accessory thru-the-bottom connections are
used, refer to the accessory installation instructions for
installation.
High-Voltage Connections (Fig. 13)
The unit must have a separate electrical service with a field-
supplied, waterproof, fused disconnect switch mounted at, or
within sight from, the unit. Refer to the unit rating plate for
maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing. Table 2 shows recommended
wire sizes based on rating plate data.
The field-supplied disconnect switchbox may be mounted on
the unit over the high-voltage inlet hole in the control corner
panel. Be sure that disconnect box and horizontal ducts do
not cover the unit rating plate.
Proceed as follows to complete the high-voltage connections
to the unit:
1. Connect ground lead to chassis ground connection
when using separate ground wire.
2. Pigtails are provided for field power connection. Use
factory-supplied splices or UL (Underwriters’ Labora-
tories) approved copper connector. Install conduit
connectors in side panel power supply knockout open-
ings indicated in Fig. 3. Route power lines through
connector to unit control box.
Table 2 — Electrical Data
LEGEND
*Used to determine minimum disconnect per NEC.
Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the overcur-
rent protective device for the unit shall be fuse or HACR breaker.
Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
Example:
Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
NOTE:
The 575-v 48TJ008-014 units are UL, Canada only.
Determine maximum deviation from average voltage.
(AB) 457 452 = 5 v
(BC) 464 457 = 7 v
(AC) 457 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%
IMPORTANT:
If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
UNIT
580D
NOMINAL
VOLTAGE
IFM
TYPE
VOLTAGE
RANGE
COMPR
(ea)
OFM
(ea)
IFM
COMBUSTION
FAN MOTOR
FLA
POWER SUPPLY
DISCONNECT
SIZE*
Min Max RLA LRA Hp FLA FLA MCA MOCP† FLA LRA
090
(7
1
/
2
Tons)
208/230-3-60
Std
187 254 14.0 91.0
1
/
4
1.4
5.8
.6
40.1/40.1 45/45 42/42 229/229
Alt 5.8 40.1/40.1 45/45 42/42 229/229
460-3-60
Std
414 508 6.4 42.0
1
/
4
0.7
2.6
.3
18.4 20 19 108
Alt 2.6 18.4 20 19 108
575-3-60
Std
518 632 5.2 39.0
1
/
4
0.7
2.6
.3
14.9 20 16 97
Alt 2.6 14.9 20 16 97
102
(8
1
/
2
Tons)
208/230-3-60 Std 187 254 16.0 137.0
1
/
4
1.4 5.8 .6 44.6/44.6 50/50 41/41 321/321
460-3-60 Std 414 508 8.3 69.0
1
/
4
0.7 2.6 .3 22.7 25 24 162
575-3-60 Std 518 632 6.4 58.0
1
/
4
0.7 2.6 .3 17.6 20 18 135
120
(10 Tons)
208/230-3-60
Std
187 254 15.8 130.0
1
/
4
1.4
5.8
.6
44.2/44.2 50/50 46/46 307/307
Alt 7.5 45.9/45.9 50/50 48/48 326/326
460-3-60
Std
414 508 7.9 64.0
1
/
4
0.7
2.6
.3
21.8 25 23 152
Alt 3.4 22.6 25 24 191
575-3-60
Std
518 632 6.6 52.0
1
/
4
0.7
2.6
.3
18.9 25 20 126
Alt 3.4 19.7 25 21 166
150
(12
1
/
2
Tons )
208/230-3-60
Std
187 254 23.0 146.0
1
/
4
1.4
10.6
.6
65.2/65.2 80/80 68/68 383/383
Alt 15.0 69.6/69.6 80/80 73/73 406/406
460-3-60
Std
414 508 10.4 73.0
1
/
4
0.7
4.8
.3
29.6 35 31 192
Alt 7.4 32.2 35 34 203
575-3-60
Std
518 632 8.3 58.4
1
/
4
0.7
4.8
.3
23.6 30 25 154
Alt 7.4 25.7 30 27 163
FLA
Full Load Amps
HACR
Heating, Air Conditioning and Refrigeration
IFM
Indoor (Evaporator) Fan Motor
LRA
Locked Rotor Amps
MCA
Minimum Circuit Amps
MOCP—
Maximum Overcurrent Protection
NEC
National Electrical Code
OFM
Outdoor (Condenser) Fan Motor
RLA
Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
7
457