User`s manual

28
Tabl e 11 580D102 Air Delivery, Vertical Discharge Units
NOTES:
1.
Boldface
indicates a field-supplied drive is required. (See Note 7.)
2. indicates a field-supplied motor and drive are required.
3. indicates maximum usable watts of a factory-supplied motor.
4. Maximum usable watts input is 2120. Extensive motor and electrical testing
on these units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown will not
result in nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to Table 9.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your representa-
tive to verify.
7. Standard motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
8. To convert watts to bhp:
Motor efficiency = .80
Tabl e 12 580D120 Air Delivery, Vertical Discharge Units
NOTES:
1.
Boldface
indicates a field-supplied drive is required. (See Note 8.)
2. indicates an alternate motor and drive is required.
3. indicates a field-supplied motor and drive are required.
4. indicates maximum usable watts of a factory-supplied motor.
5. Maximum usable watts input is 2120 with a standard motor and 2615 with an
alternate motor. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using your fan
motors up to the wattage ratings shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected. For additional
information on motor performance, refer to Table 9.
6. Values include losses for filters, unit casing, and wet coils.
7. Use of a field-supplied motor may affect wire sizing. Contact your representa-
tive to verify.
8. Standard motor drive range: 685 to 935 rpm. Alternate motor drive range:
835 to 1085 rpm. All other rpms require field-supplied drive.
9. To convert watts to bhp:
Motor efficiency = .80
AIRFLOW
(Cfm)
STANDARD BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 0.9 1.0 1.2 1.4 1.6
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
2200 499 524 580 677 652 867
717 1056 748 1165 779 1275 839 1578 905 1954
951 2266
2250 507 547 586 700 658 891
722 1097 752 1199 783 1301 843 1604 908 1989
955 2283
2300 513 562 592 723 663 916
727 1131 756 1224 786 1327 846 1630 910 2015
959 2300
2400 528 600 606 779 674 965
738 1199 766 1301 795 1404 853 1665 912 2041
967 2360
2500 542 646 619 835
686 1022 748 1258 777 1370 806 1491 859 1718 919 2093
971 2403
2550 550 669 627 867
692 1056 754 1292 783 1413 812 1543 864 1761 920 2110
974 2428
2600 557 692 634 891
698 1089 759 1327 787 1456 816 1587 868 1805
921 2136 976 2445
2700 573 747 648 956
711 1156 770 1404 798 1534 827 1665 878 1910
928 2162 983 2529
2800 588 803 662 1022
723 1233 782 1473 809 1613 837 1753 889 2023
937 2266 986 2554
2900 604 867 676 1089
737 1318 794 1560 821 1700 848 1840
900 2128 947 2377 993 2637
3000 620 932
690 1165 750 1404 806 1648 832 1788 849 1927
910 2223 958 2504 1002 2751
3100 636 1006
704 1241 764 1499 818 1744 844 1884 870 2023
920 2326 968 2620 1012 2870
3200 652 1089
718 1327 778 1595 831 1849 856 1980 882 2119
931 2428 979 2735 1023 3002
3300 668 1173
732 1413 793 1700 844 1954 869 2093
894 2232 942 2537 989 2839 1034 3121
3400 684 1258
747 1508 807 1805 857 2076
882 2206 907 2343 954 2645 1000 2948 1044 3237
3500
701 1361 762 1613 821 1910
871 2188 895 2326 919 2462 966 2751 1011 3062 1054 3340
3600
717 1465 777 1718 835 2023
885 2317 908 2453 932 2587 978 2870 1022 3165 1065 3445
3700
733 1569 792 1831
849 2136 899 2445 922 2579 945 2718 990 2987 1034 3272 1076 3544
3750
742 1630 800 1892
856 2197 907 2512 929 2653 952 2719 997 3055 1040 3333 1082 3609
3800
750 1683 807 1954
863 2257 914 2571 936 2847 958 2854 1003 3114 1045 3387 1087 3643
3900
767 1805 822 2076
877 2386 928 2702 930 2979 972 2987 1015 3244 1057 3495 1098 3733
4000
783 1927
838 2206 891 2512 942 2839 964 3187 986 3121 1028 3373 1070 3603 1110 3820
4100
800 2067
854 2343 905 2645 956 2971 978 3244 1000 3251 1042 3495 1082 3713 1122 3902
4200
817 2197 869 2479 920 2783 970 3099 992 3258 1015 3380 1055 3614 1095 3811 1134 3971
4250
826 2275 877 2554 928 2854 977 3165 999 3306 1022 3445 1062 3676 1102 3860 1140 4006
4300
834 2343 885 2629 935 2925 984 3230 1006 3313 1029 3508 1069 3728 1108 3906 1147 4036
bhp =
watts input x motor efficiency
746
AIRFLOW
(Cfm)
STANDARD AND ALTERNATE BELT DRIVE MOTORS
External Static Pressure (in. wg)
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts Rpm Watts
3000 552 661 632 810
701 956 761 1097 816 1216 871 1370 918 1482
967 1736 1010 1903 1063 2221
3100 565 708 644 859
711 1014 722 1173 825 1292 879 1447 928 1478
973 1778 1018 1971 1070 2265
3200 578 763 656 916
723 1081 782 1241 835 1378 887 1517
937 1745 981 1861 1026 2048 1075 2318
3300 591 818 668 973
734 1148 793 1310 845 1465 895 1595
946 1828 991 1963 1032 2099 1080 2380
3400 605 883 680 1047
745 1216 803 1387 856 1552 904 1691
953 1912 1000 2074 1041 2203 1083 2389
3500 619 948
691 1106 755 1284 813 1465 867 1648 914 1796
961 1997 1009 2177 1051 2318 1090 2469
3600 633 1022
703 1173 766 1353 824 1543 877 1744 924 1901
970 2099 1017 2282 1061 2451 1099 2596
3700 648 1106
714 1241 777 1430 835 1639 887 1831 935 2015
980 2212 1024 2380 1069 2587 1109 2735
3800 662 1190
726 1310 789 1526 846 1726 897 1927
946 2169 989 2326 1033 2487 1077 2698 1118 2895
3900 677 1284
738 1387 801 1613 857 1823 908 2023
956 2282 1000 2460 1042 2624 1085 2819 1127 3049
4000
692 1378 750 1473 813 1718 868 1919 918 2119
967 2397 1010 2587 1052 2763 1093 2933 1142 3187
4100
707 1482 762 1560 825 1814 878 2015
929 2282 977 2505 1021 2726 1062 2914 1102 3097 1155 3373
4200
722 1595 775 1656 837 1910 889 2119
941 2397 987 2624 1032 2866 1072 2971 1110 3244 1169 3576
4300
737 1718 787 1761 848 2006
900 2273 952 2523 999 2744 1042 3010 1081 3141 1118 3396 1185 3794
4400
752 1840 800 1875 860 2110
912 2397 962 2642 1008 2885 1054 3158 1091 3276 1126 3553 1201 4029
4500
768 1980 814 1989
871 2265 924 2523 973 2772 1019 3029 1067 3325 1101 3414 1134 3715 1219 4281
4600
783 2119 827 2110
883 2380 937 2661 983 2904 1030 3155 1079 3497 1111 3555 1142 3883 1237 4548
4700
799 2309 841 2291 894 2496 949 2800 994 3049 1042 3296 1092 3678 1122 3700 1150 4056 1257 4832
4800
814 2469 855 2424 906 2624 961 2952 1003 3186 1052 3440 1105 3866 1132 3848 1158 4235 1277 5133
4900
——
868 2578 918 2754 972 3088 1013 3333 1063 3589 1119 4061 1143 3999 1166 4419 1299 5449
5000
——
883 2735 931 2904 985 3226 1024 3489 1075 3741 1133 4263 1154 4154 1174 4608 1322 5782
bhp =
watts input x motor efficiency