Specifications

Loveland Fire/Rescue
Pumper
Production Specification
SVI #769 Page 108 of 125 June 17, 2010
..\4) Pricing & Change Orders\Production Change Order.pdf
Installer Supplied Items
The Advantus 3 system includes the major components required for installation with the exception of the following which
are to be supplied by the installer:
1. Foam Concentrate Supply Line(s)
Hose(s) and fittings that run from the foam tank to the foam pump inlet should be a minimum of ¾” inside diameter,
depending upon the viscosity of the foam concentrate(s) to be used. Hose and fittings must be rated for a minimum of
23 inches (584.2 mm) Hg of vacuum and 50 PSI (3 BAR) of pressure. The hose and fittings must made of corrosion
resistant material and be compatible with the foam concentrates to be used. Foam supply hose shall have a clear
wall as required by NFPA to allow viewing of foam priming operations.
2. Foam Concentrate Discharge Line
Hose(s) and fittings that are routed from the foam pump to the foam injection check valve should be a minimum of ½”
inside diameter and have a rated working pressure of at least 450 PSI (32 BAR). If the high pressure option is
selected, the rated working pressure of the hose and fittings shall be at least 600 PSI (41 BAR). The foam discharge
hose and fittings must made of corrosion resistant material and be compatible with the foam concentrates to be used.
3. Foam Concentrate Tank(s)
Foam concentrate tank(s) shall be supplied that suit the application and needs of the end user. The foam concentrate
tank(s) should meet the minimum requirements as published in the applicable NFPA apparatus standards.
4. Electrical Supply
Electrical wiring and circuit protection must be supplied and connected to the apparatus master electrical system as
described in the installation manual.
Warranty
The system shall have a two-year limited manufacturer’s warranty.
Foam shall be provided to the following discharges:
Discharges
Two (2) 1¾” Rear Hose Bed Pre-Connected Discharges
One (1) Booster Reel Discharge
One (1) Front Bumper 1¾” Discharge
One (1) Rear Hose Bed ” Alley Pre-Connected Discharge
PLUMBING SPECIFICATIONS
The fire pump plumbing system shall be of rigid or flexible piping with stainless steel fittings. Victaulic couplings shall be
installed to permit flexing of the plumbing system and allow for quick removal of piping or valves for service. Flexible hose
couplings shall be threaded stainless steel or Victaulic connections.
The fire pump and plumbing shall be hydrostatically tested in compliance to applicable sections of NFPA standards, with
test results submit with the delivery documentation.