Specifications
Loveland Fire/Rescue
Pumper
Production Specification
SVI #769 Page 111 of 125 June 17, 2010
..\4) Pricing & Change Orders\Production Change Order.pdf
STREETSIDE INTAKE
There shall be one (1) 2½” gated intake(s) located on the streetside of the apparatus. Each 2½” intake shall terminate
with a 2½” NSTF chrome plated swivel adapter. There shall be one (1) 2½” NSTM chrome plated plug and chain for each
intake.
Each intake shall include:
One (1) Akron Brass 8000 series, 2½” valve(s)
- Valve(s) shall be controlled with a swing type handle for direct valve operation through the pump operators
panel.
One (1) Innovative Controls model 3003000, ¾” brass 90 degree ball type drain valve with lift handle fitting and
color coded labels shall be provided for the above plumbing item. The valve shall be able to manually open the
drain valve when the line is under pressure and will be located on pump panel and plumbed to drain the lowest
point in the plumbing.
CURBSIDE INTAKE
There shall be one (1) 2½” gated intake(s) located on the curbside of the apparatus. Each 2½” intake shall terminate with
a 2½” NSTF chrome plated swivel adapter. There shall be one (1) 2½” NSTM chrome plated plug and chain for each
intake.
Each intake shall include:
One (1) Akron Brass 8000 series, 2½” valve(s)
- Valve(s) shall be controlled with a swing type handle for direct valve operation through the pump operators
panel.
One (1) Innovative Controls model 3003000, ¾” brass 90 degree ball type drain valve with lift handle fitting and
color coded labels shall be provided for the above plumbing item. The valve shall be able to manually open the
drain valve when the line is under pressure and will be located on pump panel and plumbed to drain the lowest
point in the plumbing.
TANK TO PUMP CHECK VALVE
There shall be a check valve between the pump suction and the booster tank valve. The check valve shall eliminate back
flow into the water tank when the pump is connected to a pressurized source.