User`s manual

5 - 19
5
Address Byte
Default
Function
Details
No.
Page
1
Bits 0 to 3
00
0
Acceleration/deceleration curve (00 to 99%)
Jog operation mode
4 to 7 0
Operation at software limit error
Sets the S-curve coefficient within range 00 to 99%. (ramp when "00" is set)
0: No 1-second wait, 1: 1-second wait
0: Deceleration stop 1: Immediate stop
2:
Software limit disabled (used when coordinate management in speed control is endless)
0074
0075
Bits
0 to 3
0
0
General-purpose input
operation mode setting
0:
Regular input (Operation state of general-purpose input relays is monitored.)
1:
Interrupt input (Speed control is switched to position control at .)
2: External startup input
(Both external startup and startup by the internal startup relay are enabled.)
0076
4 to 7
General-purpose output
operation mode setting
0:
Regular output (State of general-purpose output relays is output.)
1: Interrupt output
(ON or OFF when present value matches
the interrupt output position data)
Interrupt output ON/OFF setting follows the setting of the "A/I" bit.
0077 1 00
Parameter common setting
(X-axis parameter only enabled)
0: Axis independent parameters
1: X-/Y-axis common parameters
2: X-/Y-/Z-axis common parameters (14PS)
3: X-/Y-/Z-/A-axis common parameters (14PS)
5-23
(2) Parameter 2 (special parameters: must be set independently on each axis)
This parameter must be set when special control such as an electronic gear or absolute control (*)
using an absolute value encoder is performed. The following table shows the settings of parameter 2.
These settings must be transferred to block No.01 of the PS block data. Do not set this parameter 2
when special control is not performed. "****" in "B+****" (where B is the leading address of parameter
2) is indicated as the numerical value of the following addresses.
* Only connectors made by specified manufacturers can be used for connecting the absolute
value encoder and absolute value control driver. (See absolute value control.)
0000 1 00
Closed loop control mode
selection
0001 1
10002
99
00
Compensation time
Encoder count direction
Setting range = 01 to 99 (0.1 to 9.9 secs, in 0.1-sec increments)
00: Count incremented by CW rotation,
01: Count incremented by CCW rotation
0003 1 00 Reserved area
1 to 9999999
1 to 9999999
1 to 9999999
1 to 9999999
0004 to 0007
4
00000000
Closed loop control allowable
range (unsigned)
0014 to 0017
4 00 Reserved area
0020 1 00
Absolute value control mode
selection
0021
0022 to 0027
0030 to 0033
0034 to 0037
0040 to 0043
0044 to 0047
0050 to 0077
1
6
4
4
4
4
24
00
00
00000001
00000001
00000001
00000001
00
Absolute value control driver model selection
Reserved area
00: Model 1 (made by Wako Giken)
Instruction value M coefficient
Instruction value D coefficient
Encoder M coefficient
Encoder D coefficient
00: Closed loop control "Disabled"
If wired, the number of pulses from the encoder
can be counted.
01: Operation stops due to an error when the number
of pulses from the encoder exceeds the closed
loop control allowable range. Compensation by
closed loop control is not performed.
02: Operation stops due to an error when the number
of pulses from the encoder exceeds the closed
loop control allowable range. Compensation by
closed loop control is performed.
Sets the allowable range for the difference (deviation)
between the instruction value and the encoder pulse.
Setting range = 0000001 to 9999999
Default is no comparative judgment OFF (no error).
0010 to 0013
4
00000000
Completion pulse allowable
range (unsigned)
This is used in closed loop control mode 1 or 2. Set
the allowable range in which the feedback pulse is
input at the final coordinate.
An error occurs if the feedback pulse does not fall in
this range within the positioning monitoring time after
pulse output.
Setting range = 0000001 to 9999999
00: Absolute value control "Disabled"
01: Operation mode 1
The present value is rewritten at power ON or when the
absolute present value read relay turns ON.
5-25
Address Byte
Default
Function
Details
No.
Page
Electronic
gear 2
Electronic
gear 1
Reserved area