www.enc.net.cn/en Tel/Fax:86-755-26984485/26985120 5 Function parameter schedule graph
43
F0.11 Lower limit freq. 0.00Upper limit freq. 0.01Hz 0.00Hz ×
F0.12
Lower limit freq.
run mode
0: run at lower limit freq.
1: stop by slow down
2: free stopThe inverter cut off output, the motor
stop freely
1 0 ×
F0.13
Torque boost
mode
0: manual boost
1: automatic boost
1 0
F0.14 Torque boost 0.012.0 (%) 0.1(%) 2.0(%)
F0.15 V/F curve setting
0: constant torque curve
1: degressive torque curve 1(the 2.0nd power)
2: degressive torque curve 2 (the 1.7th power)
3: degressive torque curve 3 (the 1.2th power)
4: End-user sets VF curve himself(determined by
F2.37~F2.44)
F2.37 VF Freq. value 0
F2.38 VF voltage value 0
F2.39 VF Freq. value 1
F2.40 VF voltage value 1
F2.41 VF Freq. value 2
F2.42 VF voltage value 2
F2.43 VF Freq. value 3
F2.44 VF voltage value 3
Remark: VF frequency and voltage can’t be 0
or maximum
1
0.01Hz
0.01%
0.01Hz
0.01%
0.01Hz
0.01%
0.01Hz
0.01%
0
10.00Hz
20.00%
20.00Hz
40.00%
25.00Hz
50.00%
40.00Hz
80.00%
×
F0.16 G/P type setting
0: G type
1: P type
1 0 ×
F1Start, stop, braking function parameter group
Function
code
Name Set range
Min.
unit
Factory
default
Modifi
-cation
F1.00 Start run mode
0: start from starting freq.
1: first brake, then start from starting freq.
2: Start after inspecting speed
1 0 ×
F1.01 starting freq. 0.010.00Hz 0.01Hz 0.00Hz
F1.02
starting freq.
duration time
0.020.0S 0.1s 0.0s
F1.03
DC brake volt.
when starting
015(%) 1 0
F1.04
DC brake time
when starting
0.020.0s 0.1s 0.0s
F1.05 Stop mode
0: Dece stop
1: free stop
2: DeceDC brake stop
1 0 ×
F1.06
DC brake
initiative freq.
when stop
0.015.00Hz 0.01Hz 0.00Hz
F1.07
DC brake time
when stop
0.020.0s 0.1s 0.0s
F1.08
DC brake voltage
when stop
015(%) 1 0