Datasheet

15
* Recommended fastening plate
Omron corporation End plate PFP-M
IDEC corporation DIN rail stops BNL6, BNL8
Matsushita electric works, LTD Fastening plate ATA4806
(1) Hook (1) of DCL-33A on the upper side of the DIN rail. (Fig. 9.4-1)
(2) Making the (1) part of the DCL-33A as a support, fit the lower part of the DCL-33A to the DIN rail.
DCL-33A will be completely fixed to DIN rail with a “Click” sound. (Fig.9.4-1)
(Fig.9.4-1)
10. Wiring
Warning
Turn the power supplied to the instrument OFF before wiring or checking.
Working or touching the terminal with the power switched ON may result in an
Electric Shock which could cause severe injury or death.
Caution
• Do not
drop wire chips into DCL-33A when wiring, because they could cause fire, malfunction and trouble
• Insert the connecting cable into the designated connector securely to prevent malfunction, or it
may cause malfunction due to imperfect contact.
• Connect the AC power wiring to the designated terminal as is written in this Instruction manual, or
it may burn and damage
DCL-33A.
• Tighten
the terminal screw with the specified torque, o
r damage the terminal screw and deform the case.
• Use thermocouple
and compensating lead wire that fit sensor input specification of this unit.
• Use 3-wire RTD that fits sensor input specification of this unit.
• Do not
confuse the polarity when using DC voltage and current input in the case 24Vdc is used.
• Keep
input wire (Thermocouple, RTD) away from power source and load wire when wiring.
• To prevent the unit from harmful effects of the unexpected level noise, it is recommended that a
surge absorber to be installed between the electromagnetic switch coils.
• This
unit has neither built-in power switch nor fuse. Therfore it is necessary to install them in the circuit
near the external unit.
(Recommended fuse: Rated voltage 250Vac,Rated current: 2A,Fuse type: Time-lag fuse)
(1)
(2)