Datasheet

16
* Note
Tighten the terminal screw properly referring to the table below.
Terminal screw
Terminal No.
Torque
M2.6 (1) to (4)
Max. 0.5Nm
M2.0 (5) to (9)
Max. 0.25Nm
Terminal arrangement
(Fig.10-1)
R/ : Relay contact output
S/ : Non-contact DC voltage output
A/ : DC current output
Event output (Open collector output)
Outputs when alarm, Loop break alarm or
Heater burnout alarm [Option] is ON.
(Fig.10-2)
• Option: Heater burnout alarm output
This alarm is not available for detecting current under
phase control.
Use the current transformer (CT) provided, and pass
a lead wire of the heater circuit into a hole of the CT.
When wiring, keep the CT wire away from any AC
source or load wires to avoid the external interference.
(Fig.10-3)
11. Specifications
11.1 Standard specifications
Model name DIN rail mounting type indicating controller
Mounting method DIN rail mounting method
Setting method Membrane sheet key
Display PV display: Red LED 4-digit Character size: 7.5 x 4.1mm (H x W)
SV display: Green LED 4-digit Character size 7.5 x 4.1mm (H x W)
24Vac or
100 to 240Vac
Power
24Vdc
(1) (2)
+ -
-A/
-S/
-R/
(3) (4)
+ -
(8) (9)(5) (6) (7)
+ - + -
A B B
TC
RTD
Vdc
mAdc
Event output
(EVT)
(1) (2) (3) (4)
(5) (6) (7)
(5) (6) (7)
CT input socket
Power
supply
Heater
CT
Lower part of main body
CTinputW
Communication
C5
(RS-485)
(1)
(2)
(3)
(4)
(5)
(6)
COM
NC
YA(-)
YB(+)
NC
COM
(1) (6)
(8) (9)
+ -