Datasheet

2
2. Name and functions of the sections
(1) Event (EVT) output action indicator
A red LED lights when Event output [Alarm, Loop break alarm or Heater burnout alarm (Option)]
is ON.
(2) Control output (OUT) action indicator
A green LED lights when the control output (OUT) is ON.
(3) Serial communication output indicator
A yellow LED blinks while serial communication TX (sending) is output.
(4) PID auto-tuning action indicator
A yellow LED blinks while PID auto-tuning is performing.
(5) PV display
Indicates actual temperature (PV) with a Red LED.
(6) SV display
Indicates setting value (SV) with a Green LED.
(7) key
Increases numeric value on the SV display or switches the selected item.
(8) key
Decreases numeric value on the SV display or switches the selected item.
(9) key
Changes the setting mode or registers setting value and the selected value.
(Resisters the setting value and selected value by pressing the key.) (Fig. 2-1)
(10) key
Selects the setting item with the key.
3. Operation
The sensor input character and temperature unit are indicated on the PV display for approx. 3
seconds after the power is turned on, and the rated scale maximum value is indicated on the
SV display. (Table 3.1-1)
(If the other value is set in the scaling high limit value, it is indicated on the SV display.)
During this time all outputs and the LED indicators are on their OFF status. After a while
control starts indicating actual temperature on the PV display and setting value on the SV display.
(Table 3.1-1)
Input Scale range Resolution
M
K
0 to 1370 0 to 2500 1 ( )
0.0 to 400.0 0.0 to 750.0 0.1 ( )
J
0 to 1000 0 to 1800 1 ( )
R
0 to 1760 0 to 3200 1 ( )
S 0 to 1760 0 to 3200 1 ( )
B
0 to 1820 0 to 3300 1 ( )
E
0 to 800 0 to 1500 1 ( )
T -199.9 to 400.0 -199.9 to 750.0 0.1 ( )
N 0 to 1300 0 to 2300 1 ( )
PL-II 0 to 1390 0 to 2500 1 ( )
C(W/Re5-26)
0 to 2315 0 to 4200 1 ( )
Pt100
-199.9 to 850.0 -199.9 to 999.9 0.1 ( )
-200 to 850 -300 to 1500 1 ( )
JPt100
-199.9 to 500.0 -199.9 to 900.0 0.1 ( )
-200 to 500 -300 to 900 1 ( )
4 to 20mA
-1999 to 9999 *1, *2 1
0 to 20mA
-1999 to 9999 *1, *2 1
0 to 1V
-1999 to 9999 *1 1
*1: Scale range and
decimal point place
can be selected
*2: Needs to connect 50
shunt resistor (separately
sold) between input
terminals.
(1)
(2)
(5)
(6)
(3)
(4)
(7)
(8)
(9)
(10)