12. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply and wiring.
Indication
Phenomenon
Presumed cause and solution
” is blinking on the PV
display.
Sensor
(Thermocouple, RTD and DC voltage
[0 to 1Vdc] input) is burnt out.
Change the sensor for new one.
The lead wire of the sensor
(Thermocouple, RTD and DC
voltage [0 to 1Vdc] input ) is not securely connected.
Connect it to the terminal properly.
The indication on the PV display
does not change.
Sensor (DC current [0 to 20mAdc] and DC voltage
[0 to 10Vdc]) is burnt out.
Change the sensor for the new one.
The
lead wire of the sensor (DC current [0 to 20mAdc] and
DC voltage [0 to 10Vdc] is not securely connected to the
terminal.
Connect the sensor lead wire securely to the instrument
terminal.
” is blinking on the PV
display.
Sensor
(DC current [4 to 20mAdc] and DC voltage[1 to 5Vdc]
input) is burnt out.
Change the sensor for the new one.
The sensor lead wire is not securely connected to the
terminal (DC current
4 to 20mAdc) and DC voltage
[1 to 5Vdc]
Connect the sensor lead wire securely to the terminal of
the instrument.
The indication on the PV display
is abnormal or unstable.
Designation
of the sensor (input) is incorrect.
Set the correct sensor (input).
The
polarity of the sensor input is incorrect.
Wire it correctly.
Temperature unit (
/ ) is mistaken.
Set the correct unit.
AC
is leaking from controlled object to thermocouple or RTD.
Keep AC from leaking into the controlled object.
” is indicated on the
PV display.
Internal memory is out of order.
Please contact our sales branch or the shop where you
purchased this unit.
Key operation
Phenomenon
Presumed cause and solution
Setting values do not change
even if the or key is
pressed during setting mode
Mode1
or mode 2 is selected in setting value lock selection.
Cancel the Lock mode.
PID auto-tuning is performing.
Cancel PID auto-tuning.
Unable to set the value beyond
or below scaling high limit or low
limit within the rated scale range
even if the or key
is pressed.
The
value of scaling high limit setting or low limit setting in
auxiliary function setting mode 2 is set to still one.
Set the proper value.
• If you have any inquiries, please consult our agency or the shop where you purchased the unit.
SHINKO TECHNOS CO.,LTD.
OVERSEAS DIVISION
:
:
:
:
Reg. Office
Mail Address
URL
E-mail
2-48, 1-Chome, Ina, Minoo, Osaka, Japan
P.O.Box 17, Minoo, Osaka, Japan
http://www.shinko-technos.co.jp
overseas@shinko-technos.co.jp
Tel :
Fax:
81-727-21-2781
81-727-24-1760