Datasheet

4
3.2 Main setting mode
Character
Name, Description, Setting range
Initial value
Main setting
Set the value for controlled objects.
Scaling low limit setting value to Scaling high limit setting value
(Decimal point place follows the selection for DC current input)
M: 0
3.3 Sub setting mode
Character
Name, Description, Setting range
Initial value
PID auto-tuning Perform/Cancel
Performs
PID auto-tuning. However when PID auto-tuning does
not finish after 4 hours it started, PID auto-tuning is shut down
compulsory.
PID cancellation :
PID auto-tuning performing:
Proportional band setting
Sets the p
roportional band.
ON/OFF action when setting the value to 0.0
0.0 to 110.0%
2.5%
Integral time setting
Sets the
integral time.
Setting the value to 0 disables this function.
This
setting item is not indicated for ON/OFF action.
0 to 1000 seconds
200 seconds
Derivative time setting
Sets the derivative time.
Setting the value to 0 disables this function.
This
setting item is not indicated for ON/OFF action.
0 to 300 seconds
50 seconds
Anti-reset windup setting
Sets
anti-reset windup.
This
setting item is indicated only for PID action.
0 to 100%
50%
Proportional cycle setting
Sets the proportional cycle value for the control output
(OUT).
This
setting item is not indicated for ON/OFF action or DC
current output.
1 to 120 seconds
R : 30
seconds
S : 3 seconds
Manual reset setting
Sets the resetting value manually.
This
setting item is indicated only for P and PD action.
Proportional band converted value (In the case of DC voltage
and current input, decimal point place follows the selection.)
M: 0.0
Alarm setting
Sets the action point for the alarm output.
Setting the value to 0 or 0.0 disables this function.
(excluding Process high and Process low alarm)
When Loop break alarm and Heater burnout alarm are applied
together, the output is common.
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
See (Table 3.3-1). (In the case of DC voltage and DC current
input, decimal point place follows the selection.)
M: 0