Character
Name, Description, Setting range
Initial value
Heater burnout alarm setting
Sets the heater current value for
Heater burnout alarm.
Setting the value to 0.0 disables this function.
Self-holding is not available for the alarm output.
When
alarm and Loop break alarm are applied together,
the output is common.
This setting item is not indicated when [Option: W] is not added.
Rating
5A : 0.0 to 5.0A
Rating
20A: 0.0 to 20.0A
Rating
10A: 0.0 to10.0A
Rating
50A: 0.0 to 50.0A
0.0A
Loop break alarm time setting
Sets the time to assess the Loop break alarm.
Setting the value to
0 disables this function.
When
alarm and Heater burnout alarm are applied together,
the output is common.
0 to 200 minutes
0 minutes
Loop break alarm action span setting
Sets the action span to assess the Loop break alarm.
Setting the value to
0 disables this function.
When
alarm and Heater burnout alarm are applied together,
the output is common.
Thermocouple and RTD input
0 to 150 ( ) or 0.0 to 150.0 ( )
DC voltage and DC current input
0 to 1500 (Decimal point place follows the selection)
M: 0
(Table 3.3-1)
Alarm action type Setting range
High limit alarm -(Scaling span) to Scaling span -side minimum
setting value
-199.9 or -1999
+side maximum
setting value
999.9 or 9999
Low limit alarm -(Scaling span) to Scaling span
High/Low limits alarm 0 to Scaling span
High/Low limit range alarm 0 to Scaling span
Process high alarm Scaling low limit setting value to high limit value
Process low alarm Scaling low limit setting value to high limit value
High limit alarm w/standby -(Scaling span) to Scaling span
Low limit alarm w/standby -(Scaling span) to Scaling span
High/Low limits w/standby 0 to Scaling span
3.4 Auxiliary function setting mode 1
Character
Name, Description, Setting range
Initial value
Setting value LOCK designation
Locks
the setting value to prevent setting errors.
The setting item to be locked is dependent on the designation.
PID
auto-tuning cannot be carried out when Lock1 or Lock2
is selected.
(Unlock): All setting values can be changed.
(LOCK 1): None of setting values can be changed.
(LOCK 2): Only main setting mode can be changed.
Unlock
(LOCK 3): All setting values can be changed except Controller/Converter
function selection. However they return to their former value
after power is turned off because they are not saved in the
non-volatile memory. (Be sure to select LOCK 3 when using
with PC-900 [SVTC attached])