Datasheet

6
Sensor correction setting
Sets the sensor correction value of the sensor.
Thermocouple and RTD input: -100.0 to 100.0 ( )
DC voltage and DC current input: -1000 to 1000 (Decimal point
place follows the selection.)
M: 0.0
Instrument number setting
Sets the instrument number individually to each instrument
when connecting multiple instruments via serial communication.
This setting item is indicated only when [Option: C5] is added
0 to 95
0
Data transfer rate selection
Selects the data transfer rate to meet the rate of host computer.
This setting item is indicated only when [Option: C5] is added
2400bps: , 4800bps: , 9600bps: , 19200bps:
9600bps
3.5 Auxiliary function setting mode 2
Character
Name, Description, Setting range
Initial value
Selects the
sensor type and temperature unit.
K (0 to 1370 )
Input Character
K
0 to 1370 : 0 to 2500 :
0.0 to 400.0 : 0.0 to 750.0 :
J 0 to 1000 : 0 to 1800 :
R 0 to 1760 : 0 to 3200 :
S 0 to 1760 : 0 to 3200 :
B 0 to 1820 : 0 to 3300 :
E
0 to 800 : 0 to 1500 :
T
-199.9 to 400.0 :
-199.9 to 750.0
:
N 0 to 1300 : 0 to 2300 :
PL- 0 to 1390 : 0 to 2500 :
C(W/Re5-26)
0 to 2315 : 0 to 4200 :
Pt100
-199.9 to 850.0 :
-199.9 to 999.9
:
-200 to 850 : -300 to 1500 :
JPt100
-199.9 to 500.0 :
-199.9 to 900.0
:
-200 to 500 :
-300 to 900 :
4 to 20mA
-1999 to 9999:
0 to 20mA
-1999 to 9999:
0 to 1V
-1999 to 9999:
Scaling high limit setting
Sets the scaling high limit value.
Scaling low limit
setting value to Input range maximum value
(DC voltage and current input: Decimal point place follows the
selection.)
M: 1370
Scaling low limit setting
Sets the scaling low limit value.
Input
range minimum value to Scaling high limit setting value
(When DC voltage and DC current inputdecimal point place
follows the selection.)
M: 0
Decimal point place selection
Selects the decimal point place.
However, when thermocouple or RTD input is selected in
sensor selection, this setting item is not indicated.
No decimal point
to the 3
rd
digit after decimal point
Decimal
point omitted