Character
Name, Description, Setting range
Initial value
PV filter time constant setting
Sets the
PV filter time constant.
If the setting value is too large, it affects control result due to
the response delay.
0.0 to 10.0 seconds
0.0 seconds
Control output high limit setting
Sets the control output high limit value.
This setting item is not indicated when
ON/OFF action.
Control output low limit
to 105%
Setting greater than 100% is effective to DC current output type
100%
Control output low limit setting
Sets the control output low limit value.
This
setting item is not indicated during ON/OFF action.
-5% to control output high limit
Setting less than 0% is effective to DC current output type.
0%
Control output ON/OFF action hysteresis setting
Sets the
ON/OFF action hysteresis for the control output.
This setting item is indicated only for ON/OFF action (P=0)
Thermocouple and RTD input: 0.1 to 100.0 ( )
DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)
M: 1.0
Alarm action selection
Selects alarm action type.
No alarm :
High limit alarm :
Low limit alarm :
High/Low limits alarm :
High/Low limit range alarm :
Process high alarm :
Process low alarm :
High limit alarm w/standby :
Low limit alarm w/standby :
High/Low limits alarm w/standby :
No alarm
Alarm action Energized/Deenergized
Selects alarm action Energized/Deenergized.
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
Energized:
Deenergized:
Energized
Alarm HOLD function selection
Selects whether alarm HOLD function is [Used] or not.
If alarm HOLD function is set to used, once the alarm
functions alarm output remains until the power is turned off.
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
Alarm
HOLD [Not used]:
Alarm
HOLD
[Used]
:
Alarm HOLD
[Not used]
Alarm hysteresis setting
Sets the alarm hysteresis.
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
Thermocouple and RTD input : 0.1 to 100.0 ( )
DC voltage and DC current input: 1 to 1000 (Decimal point
place follows the selection.)
M: 1.0