User's Manual

RFI341 Radio Frequency Interrogator
28 SICK AG Division Auto Ident - Germany - All rights reserved 8012640/2008-03-10
5.4.6 Connecting the Switching Output
The two switching outputs are completely user defined and controlled by
special command strings as described in the document “Telegram Listing
RFI341”. The maximum load current is 400 mA. The outputs are driven with
supply power (24V DC norminal). The output drivers are powered with the
DC input voltage of nominal 24V DC and with the Dc power supply
reference. There is a direct connection between VS0 clamp to 24V DC clamp
and from Gnd0 to GND. Optional the output driver could be driven with an
external power source. Please contact the application team for further
information.
5.4.7 Ethernet
By default the IP address will be organised by the DHCP server (dynamic mode). If
it is intended to use the device in static-IP-address mode the IP address and Subnet
Mask must be programmed before according to the used sub-net. For this please use
the available parameterisation software or the related STX/ETX commands as
described in the telegram-listing.
In Stand-Alone use with a Laptop an cross cable is required and the static IP address
must be used. In standard Network configuration a standard patch cable is required.
Scematic
VS
GND
Out 1
GND
Out 2
GND
Supply Output
Output Level see 9.1
Remark: GND1 (In1) GND2 (In2) GND (Out1/2)