GREEN POINT TECHNICAL SPECIFICATIONS GREEN POINT 10-15-20kVA single-phase / single-phase 10-15-20kVA three-phase / single-phase SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 Pag.
GREEN POINT Table of contents ..1.. OBJECTIVE 3 ..2.. DESCRIPTION OF THE SYSTEM 3 ..3.. APPLICATIONS 4 ..4.. CHARACTERISTICS 4 ..5.. REFERENCE STANDARDS 10 5.1 Main reference standards 10 5.2 Standards relating to systems and installation 12 ..6.. INSTALLATION INSTRUCTIONS 6.1 Electrical system requirements 13 13 6.1.1 Protections 13 ..7.. SYSTEM BLOCK DIAGRAM 16 7.1.1 Block diagram of the UPS 10÷20kVA 16 17 7.2 Options 17 7.3 Operating modes 19 ..8.. INTERFACING 22 8.
GREEN POINT 1 - OBJECTIVE This technical document has been produced to be used by UPS system designers and installers.
GREEN POINT 3 - APPLICATIONS Personal computers Small IT networks Local Area Networks (LAN) Workstations Servers Point of sale (POS) systems Data centres Industrial PLC’s Cash registers Electro-medical equipment Emergency devices (lights/alarms) Telecommunications equipment E.
GREEN POINT The parallel system modification does not require the UPS to be manually calibrated in any way, the calibration of the systems is handled automatically by the microprocessor digital control system, this controls the exchange of information and ensures that the load distribution between the various UPS systems is equal.
GREEN POINT (on-line). When the mains supply returns to within the acceptable limits, the system will first ensure that the supply remains stable, before switching the load back onto the mains supply. During both of these operating modes, the load is powered directly from the mains supply via the bypass. However, due to the EMI filters in both the input and output, the mains supply is filtered and therefore free of any electrical disturbances.
GREEN POINT The UPS can be configured to automatically restart after a mains supply failure or after the batteries have become fully discharged. The Auto-Restart function may be delayed using the built-in software. Cold Start (no battery): Enables the UPS to be switched on during the absence of the mains supply (optional).
GREEN POINT Easy to install and maintain Simplified installation: The UPS can be connected to either a single-phase or three-phase power supply without any internal modifications necessary. Castors to ease installation, movement and maintenance of the system . Adjustable output voltage via the control panel. This enables the output voltage from the system to be increased to compensate for the drop of voltage through the cables to the load, guaranteeing the rated voltage to all users.
GREEN POINT The software enables the user to programme the automatic start-up and shutdown of the system on a weekly basis. The UPS also contains the following hardware interfaces: - double RS232 serial port voltfree contacts interface slot for the installation of a network adaptor EPO (Emergency Power Off) contact for UPS emergency power off using a remote emergency button. SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 Pag.
GREEN POINT 5 - REFERENCE STANDARDS 5.1 Main reference standards The company quality system has been certified as conforming to ISO 9001 (Certificate ITALCERT No. 005/03). This covers all of the procedures, operating methods and controls from the design stage to production, sales, through to the after sales service support.
GREEN POINT IEC61000-4-3: Immunity: electromagnetic fields IEC61000-4-4: Immunity: transient overvoltages (BURST) IEC61000-4-5: Immunity: current surges (Surge) IEC61000-4-11: Low frequency disturbances EN50141: Induced radio interference EN55022: Radio frequency disturbance EN62040-3 Uninterruptible power supply systems (UPS): performance provisions and test procedures.
GREEN POINT 5.2 Standards relating to systems and installation The above product regulations refer specifically to uninterruptible power supply systems. It is these regulations that manufacturers of uninterruptible power supply systems are obliged to adhere to. However, with regard to the electrical system, the installer must refer to other standards.
GREEN POINT 6 - INSTALLATION INSTRUCTIONS 6.1 Electrical system requirements 6.1.1 Protections UPS INTERNAL PROTECTION The size of the circuit breakers and fuses positioned in the UPS input/output lines are shown in the table below (refer to the block diagram section for an explanation of the abbreviations). Any fuse that requires replacement must only be replaced with a fuse of the same type and rating, as indicated in the table below.
GREEN POINT Differential (Residual Current Device (RCD)) In the standard version, where no input isolation transformer exists, the mains supply input neutral is connected to the UPS output neutral. The UPS does alter the arrangement of the neutral regime within the system, as a result, the electrical systems both up stream and down stream are identical. Additional differential (RCD) devices may be installed on the output of the UPS, corresponding to those installed on the input.
GREEN POINT CONNECTING THE SUPPLY AND LOAD UPS with single-phase output (three-phase + neutral input) PE L1 L2 L3 N L N PE Refer to the table below for the recommended cross sectional area of the input and output cables. The figures within the brackets are the maximum sizes that may be connected to the system terminals. Size.
SP121E Rev. 000 Siel S.p.A.
GREEN POINT 7.2 Options Isolating transformer Back-up extension Battery rechargerRemote LED display Net Adapter USB Converter Dual input Led remote mimic panel Remote mimic panel with Parallel display Active filter LEGEND : 1) Automatic By-Pass: The automatic by-pass is an SCR (static) device that automatically switches the UPS output onto the incoming mains supply in the event of an overload and/or a fault within the UPS.
GREEN POINT emergency power off (EPO) as standard (see interface section) 5) Slot for network interface or other communications cards The expansion slot enables the user to insert additional communications devices such as SNMP interfaces (network adaptor card) or an auxiliary RS232 interface card/duplexer. 6) Control and display panel The control and display panel provides the user with all of the visual (LED and LCD) and acoustic (buzzer) signals regarding the operational status of the UPS.
GREEN POINT The static bypass can support overloads greater than those supported by the inverter and enables the load to be powered even if an internal fault within the UPS occurs. The bypass has one fused at the input to the UPS. 11) Back feed protection The back feed protection is installed in series with the bypass SCRs.
GREEN POINT ON - LINE With the factory default setting, the UPS goes into ON LINE mode when switched on. Display Power message supply NORMAL OPERATION ok SWIN FBY FBAT SWOUT SWMB on on on on Led Led Led Led Buzzer BATT IN OUT BY off on on off off off MAINS present and load powered. The load is constantly supplied by the inverter with a stabilised and regulated voltage and frequency.
GREEN POINT STAND-BY FUNCTION: The UPS can be programmed to operate in stand-by mode. During this mode, the UPS output remains off whilst the mains supply is present and activates only when the mains supply fails. The inverter start up is progressive (320 msec), to prevent current surges occurring due to loads such as lights etc. SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 Pag.
GREEN POINT 8 - INTERFACING 8.1 Remote signals and command connectors The following connectors are situated on the rear. Refer to the “VIEWS OF THE UPS” section for details. 1 x EPO (emergency power off ) connection point; 1 x DB15 female REMOTE; 1 x DB9 male RS232-1; 1 x DB9 female RS232-2; 1 x Aux Slot for SNMP card etc. 8.2 EPO (Emergency Power Off command) The EPO operates a normally closed system and by opening the link will force the UPS into an emergency power off command.
GREEN POINT 8.4 DB9 female “RS 232-1” PC connection Can be used to connect the UPS to a computer 9 pin DB9 type male connector. The UPS transmission protocol preset by the factory is as follows: - 9600 baud, - no parity, - 8 bit,- 1 stop bit. The transmission speed can be configured using the CUSTOMISATION menu on the panel from 1200 to 9600 baud.
GREEN POINT 9 - OPTIONS 9.
GREEN POINT 9.2 - Communication software MAIN CHARACTERISTICS 1) Sequential and prioritised shutdown: Greenshield enables the user to shutdown the network without having to individually switch off each PC or server, and before doing so, Greenshield will save the work that was being done regardless of the application that was being used. The user may also define their own shutdown procedure and also prioritise the shutdown of critical components within the system (such as vital and non vital servers).
GREEN POINT Greenshield is the easy to use yet powerful program that enables the user to monitor and control the UPS systems. There are various graphical versions including Windows, Java, OS/2 and MacOS. 2) MACOS version The Greenshield software is the only UPS control and shutdown software available for the Macintosh that has a client-server architecture. Enabling the user to access the Windows, Novell, IBM OS/2 and the most commonly available UNIX operating systems, when using a TCP/IP network.
GREEN POINT 10 - CONTROL / DISPLAY PANEL 10.1. LED Panel BUTTONS 1. Help/Language selection 2. Measurements 3. Commands / selection / customisation 4. Events log 5. Audible alarm On/Off 6. Time / date 7. Scroll back 8. Scroll forward Control / Display panel (10-20 kVA models) Information on the UPS operating status is provided by: - a Liquid Crystal Display (LCD), with variable contrast and two lines of 40 characters.
GREEN POINT LEDs The LEDs can be either lit, flashing or off, thus providing immediate information on the UPS status. IN LED (green): input supply. Lit: The input supply is within a preset range (voltage or Frequency); Flashing: The input supply is not within a preset range (voltage or Frequency); Off: No input supply present. OUT LED (green): inverter output line. Lit: The UPS output is supplied by the inverter, if the BY (yellow) is also lit, the UPS is in Stand by mode.
GREEN POINT 10.2 Liquid Crystal Display ( LCD ) LCD display: status messages During Normal Operation mode, where no specific information has been requested and/or no particular command has been made using either the buttons on the control panel or via the RS232 remote line, the LCD will display a number of basic messages.
GREEN POINT 10.4 Alarm messages The alarm messages that appear on the first line of the display panel are listed below. The alarm number in brackets indicates the level of priority. [1] DISTURBANCES ON THE BY-PASS LINE This alarm is present whenever there is a disturbance on the by-pass line (such as a voltage peak or harmonic distortion, whilst the voltage and frequency are correct).
GREEN POINT This alarm is present if one of the following conditions occurs: − − the incoming mains supply voltage is insufficient. the output load, measured in active power [W], exceeds the rated value. [8] OUTPUT OVERLOAD Indicates that the power drawn by the load and provided by the inverter exceeds the permitted value. The value indicated, expressed in %VA, exceeds 100%. This alarm is activated whenever the peak current absorbed by the load exceeds the maximum value permitted.
GREEN POINT This transitory phase occurs, for example, when the machine has just been switched on, or when it is waiting to return to inverter mode after having been switched to by-pass mode due to an overload. [12] BY-PASS FOR OUTPUT OVERLOAD (fixed or flashing message) If the message is flashing then the alarm has been memorised. Indicates that the by-pass line overload has been memorised. The overload must persist for a certain amount of time in order for it to be memorised.
GREEN POINT This alarm is present when the total shutdown command has been activated using either the control panel or the RS232 connection. The system carries out the command after a delay of several seconds, giving the user time to cancel the command, if required. The command is memorised even when the system is shutdown due to insufficient power supply. [20] REMOTE SYSTEM OFF COMMAND: ACTIVE As per the alarm above, but with the command activated via the "REMOTE" connector.
GREEN POINT 11 - VIEWS OF THE UPS 11.1 Front and rear view of the UPS FRONT VIEW (10÷20 kVA) REAR VIEW (10÷20 kVA) E A B C D + + + + + + + + B A FUS E + FUSE + + + FRONT FRONTE SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 REAR RETRO Pag.
GREEN POINT 12 - TECHNICAL DATA 12.1 Models MODEL POWER GREEN POINT 10kVA/8kW GREEN POINT 15kVA/12kW GREEN POINT 20kVA/16kW 35 BACK-UP cosfi 0.8 0 8 11 15 0 8 11 15 0 7 10 BACK-UP cosfi 0.
GREEN POINT 12.2 Back-up expansion modules MODEL GREEN POINT 10 kVA GREEN POINT 15 kVA GREEN POINT 20 kVA SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 BACK-UP factor 0.8 30 40 BACK-UP factor 0.7 35 46 DIMENSIONS (HWD) mm 1200x450x750 1200x450x750 WEIGHT kg 160 160 65 30 35 75 35 40 1200x555x720 1200x450x750 1200x450x750 563 240 240 40 65 30 46 75 35 1200x450x750 1200x860x720 1200x450x750 240 845 240 40 45 60 46 55 70 1200x450x750 1200x860x720 1200x860x720 240 845 845 Pag.
GREEN POINT 12.
GREEN POINT MODEL INPUT 10000 15000 20000 Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase input input input input input input Frequency tolerance configuration (from the control panel) Switching time (mains to inverter synchronised) Switching time (mains to inverter not synchronised) ±5% (1% steps) Null Null Switching time in the Economy /Smart Active mode (by-pass to inverter) By-pass protection <1ms Fuse 50A/g R Fuse 50A/g R Fuse 63A/gG Fuse 63A/gG Back-feed protection 1
GREEN POINT MODEL INPUT Floating voltage End discharge voltage Battery voltage compensation for temperature Battery ripple current Battery voltage stability (batteries charged) Number of phases Rated voltage Phase/neutral voltage variation range (from control panel) Waveform 10000 15000 20000 Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase input input input input input input 434V 434V 650V 650V 650V 650V 320V 320V 480V 480V 480V 480V 1 230V 1 230V 20kVA 12kW 20kVA
GREEN POINT MODEL INPUT 10000 15000 20000 Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase input input input input input input Output frequency variation with mains present Output frequency variation (from display panel) Frequency variation velocity (Hz/sec.
GREEN POINT MODEL INPUT Compliance with safety regulations EMC compliance Immunity to sudden current surges 10000 15000 20000 Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase input input input input input input EN62040-1 Directive 73/23/EEC and 93/68/EEC EN50091-2 cl.
GREEN POINT MODEL INPUT 10000 15000 20000 Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase input input input input input input Standard remote signals Information available on display SP121E Rev. 000 Siel S.p.A. Issued date: 2005-05-06 3 volt free contacts/double serial line/EPO input + by-pass Pag.