Commissioning
6.1 Operating via the handheld programmer
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 01/2014, A5E32221411-AB
51
Space
High calibration point (process full level)
Level
Sensor reference point
a)
Distance
Low calibration point (process empty level)
a)
The point from which High and Low Calibration points are referenced: see Dimension drawings
(Page 205).
Low calibration point
Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See
Operation
for an illustration.)
Values
Range: 0.00 to 20.00 m
High calibration point
Distance from Sensor Reference Point to High Calibration Point: usually process full level. (See
Operation
for an illustration.)
Values
Range: 0.00 to 20.00 m