Parameter reference
SITRANS LR250 (FOUNDATION FIELDBUS)
154 Operating Instructions, 01/2014, A5E32221411-AB
AIFB1 (2.6.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
All AIFB parameters are read only via LUI and AMS Device Manager, and can only be
changed using a remote host such as DeltaV or NI-FBUS Configurator.
AIFB 1 and AIFB 2 are not active out of the box. These blocks will show Out of Service
on the LCD at startup. If these blocks are needed for an FF application, use a tool such
as DeltaV or NI-FBUS Configurator to configure and schedule the blocks. See
Configuration
in manual
Foundation Fieldbus for Level Instruments
(7ML19985MP01) for
further details.
Static Revision Number (2.6.1.)
The revision level of the static data associated with Analog Input Function Block 1. The Static
Revision No. is updated whenever a configuration parameter is changed.
Mode (2.6.2.)
Used to request an operating mode from the Analog Input Function Block.
Options
Auto Mode (AUTO)
Manual Mode (MAN)
Out of Service (OOS)
Allows you to put the SITRANS LR250 into Out of Service Mode and then reset it to Auto Mode.
Manual Mode can be used when simulating output. See
Simulation
in manual
Foundation
Fieldbus for Level Instruments
(7ML19985MP01) for more details.