User's Manual

Table Of Contents
Parameter reference
SITRANS LR250 (PROFIBUS PA)
112 Operating Instructions, 01/2014, A5E32221386-AB
CLEF Range (2.5.7.4.)
Note
CLEF Range is referenced from Low Calibration Point (process empty level).
The CLEF algorithm is used mainly to allow correct level reporting for low dK materials which
may otherwise cause an incorrect reading in an empty or almost empty vessel.
It is used from Low Calibration Point (process empty level ) up to the level defined by CLEF
Range (see illustration below). Above that point the Center algorithm is used. For more detail
see CLEF Range (Page 206).
Values
Range: 0 to 20 m (0 to 65.6 ft)
Default: 0.0 m
Related parameters
Position Detect (2.5.7.2.)
CLEF Range
Sensor reference point
Low calibration point (process empty level)
In applications with low dK materials we recommend setting CLEF Range to 0.5 m (1.64 ft) and
Position Detect (2.5.7.2.)
to Hybrid.
Sampling (2.5.8.)
Provides a method of checking the reliability of a new echo before accepting it as the valid
reading, based on numbers of samples above or below the currently selected echo.