Parameter reference
SITRANS LR250 (PROFIBUS PA)
98 Operating Instructions, 01/2014, A5E32221386-AB
LOE Timer (2.3.6.)
Note
When a Loss of Echo occurs Value (2.6.9.2.)
determines the material level to be reported
when LOE
Timer expires. See Loss of Echo (LOE) (Page 210) for more detail.
Sets the time to elapse since the last valid reading, before the Fail-safe material level is
reported.
Values
Range: 0 to 720 seconds
Default: 100 s
Calibration (2.3.7)
Note
We recommend using the Quick Start wizard to configure the device.