User's Manual

Table Of Contents
Parameter reference
SITRANS LR250 (HART)
118 Operating Instructions, 01/2014, A5E32220602-AB
High Calibration Pt. (2.3.2.)
Distance from sensor reference point
1)
to High Calibration Point. Units are defined in
Units
(2.2.1.).
Values
Range: 0 to 20 m. Default 0.00 m
Related parameters
Units (2.2.1.)
Near Range (2.8.1.)
When setting the High Calibration Point value, note that echoes are ignored within
Near Range
(2.8.1.)
.
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target. [see Threaded Horn Antenna with extension (Page 191), Flanged
Horn with extension (Page 196), and Flanged encapsulated antenna (3"/DN80/80A sizes and
larger) (Page 202)].
Sensor Offset (2.3.3.)
A constant offset that can be added to or subtracted from the sensor value
1)
to compensate for a
shifted sensor reference point. (For example, when adding a thicker gasket or reducing the
standoff/nozzle height.) The units are defined in
Units (2.2.1.)
.
Values
Range: -100 to 100 m. Default: 0.00 m
Related parameters
Units (2.2.1.)
1)
The value produced by the echo processing which represents the distance from sensor
reference point to the target, see
Sensor Mode (2.2.2.)
.