User's Manual

Table Of Contents
Diagnosing and troubleshooting
10.2 Device status icons
SITRANS LR250 (HART)
172 Operating Instructions, 01/2014, A5E32220602-AB
10.2
Device status icons
Icon
Priority
Level
Meaning
1
Maintenance alarm
Measurement values are not valid
2
Maintenance warning: maintenance demanded immediately
Measured signal still valid
3
Maintenance required
Measured signal still valid
1
Process value has reached an alarm limit
2
Process value has reached a warning limit
3
Process value has reached a tolerance limit
1
Configuration error
Device will not work because one or more parameters/components is
incorrectly configured
2
Configuration warning
Device can work but one or more parameters/components is incorrectly
configured
3
Configuration changed
Device parameterization not consistent with parameterization in project.
Look for info text.
1
Manual operation (local override)
Communication is good; device is in manual mode.
2
Simulation or substitute value
Communication is good; device is in simulation mode or works with
substitute values.
3
Out of operation
Communication is good; device is out of action.
Data exchanged
No data exchange