Diagnosing and troubleshooting
10.3 General fault codes
SITRANS LR250 (HART)
Operating Instructions, 01/2014, A5E32220602-AB
175
Code/
Icon
Meaning
Corrective Action
S: 9
Service interval as defined in Maintenance
Demanded Limit has expired.
Perform service.
S: 11
Internal temperature sensor failure. Repair required: contact your local Siemens
representative.
S: 12
Internal temperature of device has exceeded
specifications: it is operating outside its
temperature range.
Relocate device and/or lower process temperature
enough to cool device.
Inspect for heat-related damage and contact your
local Siemens representative if repair is required.
Fault code will persist until a manual reset is
performed using SIMATIC PDM or the LCD interface.
S: 17
Calibration interval as defined in Maintenance
Required Limit has expired.
Perform calibration.
S: 18
Calibration interval as defined in Maintenance
Demanded Limit has expired.
Perform calibration.
S: 28
* Internal device failure caused by a RAM
memory error.
Repair required: contact your local Siemens
representative.
S: 29
* EEPROM damaged. Repair required: contact your local Siemens
representative
S: 31
* Flash error. Repair required: contact your local Siemens
representative
S: 33
* Factory calibration for the internal temperature
sensor has been lost.
Repair required: contact your local Siemens
representative
S: 34
* Factory calibration for the device has been lost. Repair required: contact your local Siemens
representative
S: 35
* Factory calibration for the device has been lost. Repair required: contact your local Siemens
representative