User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR250 Overview
- Specifications
- Installation
- Wiring
- Operating via the handheld programmer
- Operating via SIMATIC PDM
- Functions in SIMATIC PDM
- Quick Start Wizard via SIMATIC PDM
- Changing parameter settings using SIMATIC PDM
- Parameters accessed via pull-down menus
- Operating via AMS Device Manager
- Functions in AMS Device Manager
- Features of AMS Device Manager
- Device Description (DD)
- Configuring a new device
- Startup
- Pull-down menu access
- Device configuration
- Quick Start Wizard via AMS Device Manager
- Maintenance and Diagnostics
- Remaining Device Lifetime [see Remaining Device Lifetime (4.2.) on page 99]
- Remaining Sensor Lifetime [see Remaining Sensor Lifetime (4.3.) on page 102]
- Service Schedule [see Service Schedule (4.4.) on page 105]
- Calibration Schedule [see Calibration Schedule (4.5.) on page 108]
- Electronic Temperature
- Wear (see Wear on page 56)
- Communication
- Security
- Device Diagnostics
- AMS Menu Structure
- Functions in AMS Device Manager
- Parameter Reference
- 1. Quick Start
- 2. Setup
- 3. Diagnostics
- 4. Service
- 5. Communication
- 6. Security
- 7. Language
- Appendix A: Alphabetical Parameter List
- Appendix B: Troubleshooting
- Appendix C: Maintenance
- Appendix D: Technical Reference
- Principles of Operation
- Echo Processing
- Analog Output
- Maximum Process Temperature Chart
- Process Pressure/Temperature derating curves
- Loop power
- Appendix E: Application Examples
- Appendix F: HART Communications
- Appendix G: ATEX Certificates
- Appendix H: Firmware Revision History
- Glossary
- Index
- LCD menu structure
Page 94 SITRANS LR250 (HART) – INSTRUCTION MANUAL 7ML19985JE03
mmmmm
Parameters
2.8.7. TVT setup
2.8.7.1. Auto False Echo Suppression
Used together with Auto False Echo Suppression Range (2.8.7.2.) to screen
out false echoes in a vessel with known obstructions.
A ’learned TVT’ (time
varying threshold) replaces the default TVT over a specified range. See
Auto False Echo Suppression (2.8.7.1.) on page 130 for a more detailed
explanation.
a) Determine Auto False Echo Suppression Range. Measure the actual
distance from the sensor reference point to the material surface
using a rope or tape measure.
b) Subtract 0.5 m (20") from this distance, and use the resulting value.
Note: Default settings in the parameter tables are indicated with an asterisk
(*) unless explicitly stated.
Notes:
• Make sure material level is below all known obstructions when Auto
False Echo Suppression is used to learn the echo profile. (An empty or
almost empty vessel is recommended.)
• Note the distance to material level when Auto False Echo learns the
environment. Set Auto False Echo Suppression Range to a shorter
distance to avoid the material echo being screened out.
• Set Auto False Echo Suppression and Auto False Echo Suppression
Range during startup, if possible.
• If the vessel contains an agitator it should be running.
• Before adjusting these parameters, rotate the instrument for best
signal (lower false-echo amplitude).
Before Auto False Echo Suppression
default TVT
TVT
Hover
Level
Level (db)
echo marker
material level
false echo