7ML19985JE03 SITRANS LR250 (HART) – INSTRUCTION MANUAL Page 103
mmmmm
Parameters
Time Units
4.3.1. Lifetime Expected
Allows you to override the factory default.
4.3.2. Time in Operation
The amount of time the sensor has been operating. Can be reset to zero after
performing a service or replacing the sensor.
To reset to zero:
In SIMATIC PDM, open the menu Device Maintenance, click on the
Remaining Sensor Lifetime tab, and click on Sensor Replaced to restart
the timer and clear any fault messages.
Via the handheld programmer, manually reset Time in Operation (4.3.2.) to
zero.
Options
a)
a)
Selectable only via SIMATIC PDM.
Hours; days; years
Default: years
Note: The device always operates in years. Changing the units affects only
the parameter view of Remaining Sensor Life parameters in SIMATIC PDM.
Values
Units
a)
: hours, days, years
a)
Units are selectable only via SIMATIC PDM.
Range: 0 to 20 years
Default: 10.00 years