Quick Start: local
Level application example
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks
to empty.
Fill rate = 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time]
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
Quick Start Parameter Setting Description
Material (1.2.) LIQUID
Response Rate (1.3.) SLOW Resets Fill Rate and Empty Rate to 0.1 m/minute.
Units (1.4.) m
Operation Mode (1.5.) LEVEL Material level referenced from Low Cal. Point.
Low Calibration Point (1.6.) 15.5 Process empty level.
High Calibration Point (1.7.) 1.0 Process full level.
Apply? (Apply changes) (1.8.) YES Save new settings.
sensor
reference
point
Level
Low Cal.
Point
High Cal.
Point
15.5 m
1.0 m
SITRANS LR250