7ML19985JE03 SITRANS LR250 (HART) – INSTRUCTION MANUAL Page 41
mmmmm
SIMATIC PDM
Features of SIMATIC PDM Rev. 5.2, SP1
SIMATIC PDM Rev. 5.2 SP1 is supported only for basic configuration and troubleshooting. For
advanced features such as the Quick Start wizard, Rev. 6.0 SP3 HF2 or higher is required.
Electronic Device Description (EDD)
You can locate the EDD in Device Catalog, under Sensors/Level/Echo/Siemens Milltronics/
SITRANS LR250. Check the product page of our website at: www.siemens.com/LR250
, under
Downloads, to make sure you have the latest version of SIMATIC PDM, the most recent
Service Pack (SP) and the most recent hot fix (HF). If you need to install a new EDD see
Configuring a new device
below.
Configuring a new device
1) Check that you have the most recent EDD, and if necessary download it from the
product page of our website at www.siemens.com/LR250
. Save the files to your
computer, and extract the zipped file to an easily accessed location. Launch SIMATIC
PDM – Manager Device Catalog, browse to the unzipped EDD file and select it.
2) Launch SIMATIC Manager and create a new project for LR250. Application Guides
for setting up HART devices with SIMATIC PDM can be downloaded from the
product page of our website at: www.siemens.com/LR250
.
3) Open the menu Device – Master Reset and click on OK to perform a reset to Factory
Defaults.
4) After the reset is complete upload parameters to the PC/PG.
5) Configure the device via the Quick Start wizard.
Quick Start Wizard via SIMATIC PDM
The graphic Quick Start Wizard provides an easy 5-step procedure that configures the
device for a simple application.
Please consult the operating instructions or online help for details on using
SIMATIC PDM.
1) If you have not already done so, check that you have the most up-to-date Electronic
Device Description (EDD) for your instrument. (See
Configuring a new device
above.)
2) Launch SIMATIC Manager and create a new project for LR250. (Application Guides
for setting up HART and PROFIBUS PA devices with SIMATIC PDM can be
downloaded from the product page of our website at: www.siemens.com/LR250
).
Note: Clicking on Cancel during an upload from device to SIMATIC PDM will result in
some parameters being updated.