Page 42 SITRANS LR250 (HART) – INSTRUCTION MANUAL 7ML19985JE03
mmmmm
SIMATIC PDM
Quick Start
Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 5.
Step 1 – Identification
3) Click on Read Data from Device to upload Quick Start parameter settings from the
device to the PC/PG and ensure PDM is synchronized with the device.
4) If required, change the language for the local user interface.
5) Click on NEXT to accept the default values. (Description, Message, and Installation
Date fields can be left blank.)
Notes:
The Quick Start wizard settings are inter-related and changes apply only after you
click on FINISH AND DOWNLOAD at the end of step 5 to save settings offline and
transfer them to the device.
Do not use the Quick Start Wizard to modify individual parameters. For quick access
to echo profile parameters see
Echo Setup
on page 54, or see
Parameter Reference
on page 78 for a complete list.
•Click on BACK to return and revise settings or CANCEL to exit the Quick Start.
For a vessel with obstructions see
Auto False Echo Suppression
on page 52.
Note: The layout of the dialog boxes shown may vary according to the resolution setting
for your computer monitor.
Quick
Start