7ML19985JE03 SITRANS LR250 (HART) – INSTRUCTION MANUAL Page 47
mmmmm
SIMATIC PDM
5) In Step 5 – Summary, check parameter values. Click on BACK to return and revise
values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings
offline and transfer them to the device.
The message Quick Start was successful will appear. Click on OK.
Configuring a stillpipe application
Launch the Quick Start wizard and follow steps 1 to 2.
In step 2, select Application Type – Level in a vessel with stillpipe, Material – Liquid
Low dK, and set the stillpipe diameter as desired.
The wizard updates the propagation factor according to the pipe diameter, and
enables the CLEF algorithm for low dK liquids (see
Position Detect (2.8.4.2.)
on
page 127 for more detail).
Continue through steps 3 to 5 then click on FINISH AND DOWNLOAD to save
settings offline and transfer them to the device.