User's Manual
7ML19985FH01 SITRANS LR 400 – INSTRUCTION MANUAL DRAFT Page 53
mmmmm
Parameters (Profibus PA)
Parameters (Profibus PA)
Parameters (Profibus PA)
Device parameter,
parameter, menu
identification
Description
Factory
Setting
Setting
Possibilities
1: Auto-Setup
Language local Language of the local
user interface
English English
Deustch
Length Unit m cm
m
mm
ft
in
Nozzle height Height flange to top of
tank
0 m numerical value
Tank Height Height tank bottom to top 20 m numerical value
Level URV Full scale of level (see
Functional Dimensions
Diagram)
20 m numerical value
Level LRV Start of scale of level (See
Functional Dimensions
Diagram)
0 m numerical value
Level damping Damping of level in s 1 s numerical value
Application type Use of the vessel Liquid (store) Liquid (store)
Liquid (process)
Silo1 (solids)
Silo2 (solids)
User tank1
User tank2
1.8: Bus address Current bus address 126 numerical value
2: Display
2.1: Multi-display Display of two measured
values
Level in Sig-
nal-to-noise
ratio in dB
non-editable
2.2: Level Level of measured
medium
m non-editable
2.3: Volume Volume of measured
medium
m
3
non-editable
2.5: Current Output Value of the analog output
in mA
non-editable
3: Diagnostics