Parameters (Profibus PA)
4.2.3.7: Fix dist. list Manual input of up to nine
fixed targets
numerical values
4.2.3.9: Auto False
Echo Suppression
Learns and records the
current signal up to the
suppression distance set-
ting. These signals are
then ignored during oper-
ation
use use
record
off
4.2.3.A: Auto False
Echo Suppression
Distance
Defines the end point of
the Auto False echo
suppression distance
0 m variable
4.2.4: Level param.
4.2.4.1: Level URV = [1.5]
4.2.4.2: Level LRV = [1.6]
4.2.4.3: Level damp-
ing
= [1.7]
4.2.4.4: Min Warn
level
Limit before reach lower
limit value
0 m numerical value
4.2.4.5: MinLim level Lower limit value of the
level (See Functional
Dimensions Diagram)
0 m numerical value
4.2.4.6: MaxLim level Upper limit value of the
level (See Functional
Dimensions Diagram)
0 m numerical value
4.2.4.7: MaxWarn
level
Limit before reach upper
limit value
0 m numerical value
4.2.4.8: HYST level Hysteresis of the level
limit values
0.5 m numerical value
4.2.5: Volume param.
4.2.5.1: Volume URV Full scale of the volume
20 m
3
numerical value
4.2.5.2: Volume LRV Start of scale of the vol-
ume
0 m
3
numerical value
4.2.5.3: Volume
damping
Damping of the volume 1 s numerical value
4.2.5.4: MinWarn vol-
ume
Limit before reach lower
limit value
0 m numerical value
4.2.5.5: MinLim vol-
ume
Lower limit value of the
volume
0 m
3
numerical value
4.2.5.6: MaxLim vol-
ume
Upper limit value of the
volume
0 m
3
numerical value
Parameters (Profibus PA)
Device parameter,
parameter, menu
identification
Description
Factory
Setting
Setting
Possibilities
chap6.fm Page 57 Tuesday, October 9, 2001 2:26 PM