User's Manual

7ML19985FH01 SITRANS LR 400 – INSTRUCTION MANUAL DRAFT Page 43
mmmmm
Parameters (HART)
4.2.5.8.3: Show table
Display table
Here you can display the entered reference values sorted on levels. In the second line,
the level corresponding to the first reference value appears first and then the
corresponding volume value when you switch further. Each switching accesses a further
reference value.
4.2.5.8.4: Clear table
Delete table
If you access the “all” selection in this parameter, the entire saved table is deleted. You
can delete individual reference values with the selection “1st”, “2nd” etc. which were
displayed in parameter 4.2.5.8.3.
or
4.2.5.8: Calculate
Automatic calculation of a vessel characteristic is faster than manual entry by calibrating
or a table. However, the calculated vessel characteristic is not as accurate as a manually
calibrated characteristic – especially in the non-linear areas of the vessel in which errors
of 1 % may occur. As well, the necessary data which you can get from the design
documents of your vessel must still correspond to the real conditions.
The 4.2.5.8: Calculate parameter requires the following parameters:
4.2.5.8.1: Tank Design (F = Vertical Cylinder)
Value
selection
Value
selection
Value
Linear
Vertical cylinder
Horizontal cylinder
sphere
Note: The reference values are sorted in order of filling states and do not necessarily
correspond to the order of the value pairs you have entered.
chap6.fm Page 43 Tuesday, October 9, 2001 2:26 PM