User's Manual
7ML19985FH01 SITRANS LR 400 – INSTRUCTION MANUAL DRAFT Page 23
mmmmm
Operation
Operating examples
Example 1(HART)
The length unit should be changed from “m” to “mm.”. The starting point is the multi-
display.
Follow the path traced with a bold line in the diagram above for input. The other paths
lead to other device functions and parameters which are not required in this example.
Next to the operating path, the control elements which you need to press are indicated
and the operating steps are numbered.
2 x
5
6
Function group
4 Device data
4
Function group
3 Diagnostics
1
2
3
Function group
1 Auto-Setup
Function group
2 Display
+12,300 m
+30 dB
4. Device data
1 Units
4.1 Units
1 Length unit
6
7
8
4. Device data
2 Operating param.
4. Device data
3 Analog output
4.3 Analog output
1 AO select
4.3.1 AO select
Level
4.3 Analog output
2 Level param.
4.3.2 Level param.
1 Level URV
4.1.1 Length unit
m
4.1.1 Length unit
mm
Multi display
9
2 x
10
chap6.fm Page 23 Tuesday, October 9, 2001 2:26 PM