7ML19985FH01 SITRANS LR 400 – INSTRUCTION MANUAL DRAFT Page 27
mmmmm
Parameters (HART)
Level damping (F = 1 s)
Damping of level in s
Set the damping of the level value in seconds. It acts on the analog output, the limit value
monitor and the local display. For damping of the sensor signal, set Function 4.2.3:.
Application Type (F - Liquid [store])
Use of the vessel
Select Silo1 (solids) for tall, narrow silos. Select Silo 2 (solids) for large diameter silos typcially
used for cement. In most cases you set one of the pre-specified applications here. The user
vessels may adopt configurations which deviate from the factory settings. These are designed
for special applications loaded at the factory or by service. the following parameters cannot be
accessed when you set a user vessel: Parameter 4.2.2.2, Parameter 4.2.2.5, Parameter 4.2.2.6,
Parameter 4.2.3.1 and Parameter 4.2.3.5
Additional Parameters
2. Display
2.1: Multi-display (F = level in m
Signal to noise ratio in db)
Display of two measured values. Values determined in Parameter 4.5.1.1 (Line 1 Local) and
in Parameter 4.5.1.4 (Line 2 Local).
2.2: Level (F = m)
Current level of measured medium (set unit using Length Unit in Auto-Setup).
2.3: Volume (F = m
3
)
Volume of measured medium (set unit using Parameter 4.1.2: Volume Unit).
Value
numerical value
Value
Liquid (store)
Liquid (process)
Silo1 (solids)
Silo2 (solids)
User tank1
User tank2
chap6.fm Page 27 Tuesday, October 9, 2001 2:26 PM