Page 4 SITRANS LR 400 – INSTRUCTION MANUAL DRAFT 7ML19985FH01
mmmmm
Specifications
Specifications
SITRANS LR 400
Power
Power Supply 120 to 230 Vac, ±15%, 50/60 Hz, 6W (12VA)
or
24 Vdc, +25/-20%, 6W
Power failure: bridge of at least 1 mains period (> 20 ms)
Fuse
Fuse (both ac and dc versions)
SI1 Fast acting ceramic, 4 x 20 mm, 1A, 250 Vac
SI2 Slow-Blow, 4 x 20 mm, 0.63 A, 250 Vac
Interface
Analog output (Not applicable to Profibus PA option)
Signal range 4 to 20 mA
Upper Limit 20 to 22.5 mA adjustable
Fail signal 3.6 mA; 22 mA; 24 mA or last value
Load Max. 600 , for HART communication min. 230
Digital Output
Function Configurable as a device status or limit value
(level, volume)
Signal type Relay, either NCC or NOC function
max. DC 50 V, max. 200 mA, rating max. 5 W.
Self-resetting fuse, R
i
= 9
Electrical Isolation Outputs electrically isolated from the power supply and
from each other
Display LCD, two lines of 16 characters each,
configurable for the following displays:
level, volume, amplitude, digital output,
temperature, validity, signal-to-noise ratio
Multi–display: 2 freely selectable measured values are
displayed simultaneously
Operation4 optical control elements, finger activated, menu-guided
Note: Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications, but reserves the right to change them at any time. Please ensure these
are the most recent specifications. Contact your representative, or check our website
at www. milltronics.com for the most up-to-date information.
sitranslrd3.book Page 4 Tuesday, October 9, 2001 10:09 AM