User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR 460
- Specifications
- Installation
- Wiring
- 4-20 mA Start Up
- Local Operation
- LCD menu structure
- HART Communications
- Remote operation via PROFIBUS PA
- PROFIBUS PA Profile Structure
- Appendix A: Parameter Descriptions
- 1. Identification
- 2. Input
- 3. Output
- 5. Maintenance settings
- 6. Condensed Status Setup
- 6.1. Condensed Status Mode
- 6.1.1. Loss of Echo S0 (Status; Diagnosis)
- 6.1.2. Cable Fault S1 (Status; Diagnosis)
- 6.1.3. No Tech Power S2 (Status; Diagnosis)
- 6.1.4. Device Lifetime Maintenance Required Limit S3 (Status; Diagnosis)
- 6.1.5. Device Lifetime Maintenance Demanded Limit S4 (Status; Diagnosis)
- 6.1.8. Sensor Lifetime Maintenance Demanded Limit S7 (Status; Diagnosis)
- 6.1.9. Device Service Maintenance Required Limit S8 (Status; Diagnosis)
- 6.1.10. Device Service Maintenance Demanded Limit S9 (Status; Diagnosis)
- 6.1.11. LTB Scale S10 (Status; Diagnosis)
- 6.1.12. Internal Temp Sensor S11 (Status; Diagnosis)
- 6.1.13. Internal Temp High S12 (Status; Diagnosis)
- 6.1.16. AIFB2 PV Range S15 (Status; Diagnosis)
- 6.1.19. Calibration Schedule Maintenance Demanded Limit S18 (Status; Diagnosis)
- 6.1.30. Memory EEPROM S29 (Status; Diagnosis)
- 6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis)
- 6.1.32. Memory Flash S31 (Status; Diagnosis)
- 6.1.33. Ident Violation S32 (Status; Diagnosis)
- 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis)
- 6.1. Condensed Status Mode
- Appendix B: Technical Reference
- Appendix C: Troubleshooting
- Appendix D: Maintenance
- Appendix E: Software Revision History
- Glossary
- Index
Page 36 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
mmmmm
C: Local Operation
4. Press the Right ARROW key again, to accept the change and return to
Navigation mode.
Device calibration
Only four settings are required for a Quick Setup: High Calibration Point, Low Calibration
Point, High Level Point, and Low Level Point. (For an illustration, see
Calibration
on
page 28.)
2.3. Sensor Calibration:
2.3.1. Sensor Units (default meters)
2.3.2. Calibration Type.
2.3.3. Low Calibration Pt.
2.3.4. High Calibration Pt.
2.3.5. Unit [Level] (default percent)
2.3.6. Low Level Point
2.3.7. High Level Point
1. Go to Calibration Type and verify that "Dry" Calibration is selected.
2. Go to Low Calibration Point and enter the new value (default units are meters).
3. Go to High Calibration Point and enter the new value (default units are meters).
4. Go to Low Level Point and enter the corresponding value in percent (default is 0).
5. Go to High Level Point and enter the corresponding value in percent (default is 100).
6. SITRANS LR 460 is now ready to operate.
Values
0*
"Dry" calibration
1
"Wet" calibration (not recommended for SITRANS LR 460)