Page 36 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
mmmmm
C: Local Operation
4. Press the Right ARROW key again, to accept the change and return to
Navigation mode.
Device calibration
Only four settings are required for a Quick Setup: High Calibration Point, Low Calibration
Point, High Level Point, and Low Level Point. (For an illustration, see
Calibration
on
page 28.)
2.3. Sensor Calibration:
2.3.1. Sensor Units (default meters)
2.3.2. Calibration Type.
2.3.3. Low Calibration Pt.
2.3.4. High Calibration Pt.
2.3.5. Unit [Level] (default percent)
2.3.6. Low Level Point
2.3.7. High Level Point
1. Go to Calibration Type and verify that "Dry" Calibration is selected.
2. Go to Low Calibration Point and enter the new value (default units are meters).
3. Go to High Calibration Point and enter the new value (default units are meters).
4. Go to Low Level Point and enter the corresponding value in percent (default is 0).
5. Go to High Level Point and enter the corresponding value in percent (default is 100).
6. SITRANS LR 460 is now ready to operate.
Values
0*
"Dry" calibration
1
"Wet" calibration (not recommended for SITRANS LR 460)