Page III-50 SITRANS LR 460 (PROFIBUS PA) – INSTRUCTION MANUAL 7ML19985JM01
mmmmm
PA: Remote Operation
Acyclic Diagnostics
This consists of four bytes.
Values of the DIAGNOSIS bit:
0 = not set
1 = set
Hex values Byte Bit Description
Indication
class
a
a.
R indicates the message remains active as long as the reason for the message
exists.
A indicates the message will automatically reset after 10 seconds
0x01000000
0
0 Electronics failure R
0x02000000 1 Mechanical failure R
0x04000000 2 Motor Temperature too high R
0x08000000 3 Electronics temperature too high R
0x10000000 4 Memory error R
0X20000000 5 Measurement failure R
0X40000000 6 Device not initialized (no calibration) R
0x80000000 7 Self calibration failed R
0x00010000
1
0 Zero point error (limit position) R
0x00020000 1 Power supply failure (electrical, pneumatic) R
0x00040000 2 Configuration invalid R
0x00080000 3 New startup carried out (Warm Start) A
0x00100000 4 Restart carried out (Cold Start) A
0X00200000 5 Maintenance required R
0X00400000 6 Characterization invalid R
0X00800000 7
Set to 1 (one), if the Ident_Number of the
running cyclic data transfer and the value of
Physical Block IDENT__NUMBER_SELECTOR
parameter are different.
R
2 0 to 7 Reserved for use within the PNO
3
0 to 6 Reserved for use within the PNO
0X00000080 7 More diagnosis information is available