User's Manual
Table Of Contents
- Table of Contents
- SITRANS LR 460
- Specifications
- Installation
- Wiring
- 4-20 mA Start Up
- Local Operation
- LCD menu structure
- HART Communications
- Remote operation via PROFIBUS PA
- PROFIBUS PA Profile Structure
- Appendix A: Parameter Descriptions
- 1. Identification
- 2. Input
- 3. Output
- 5. Maintenance settings
- 6. Condensed Status Setup
- 6.1. Condensed Status Mode
- 6.1.1. Loss of Echo S0 (Status; Diagnosis)
- 6.1.2. Cable Fault S1 (Status; Diagnosis)
- 6.1.3. No Tech Power S2 (Status; Diagnosis)
- 6.1.4. Device Lifetime Maintenance Required Limit S3 (Status; Diagnosis)
- 6.1.5. Device Lifetime Maintenance Demanded Limit S4 (Status; Diagnosis)
- 6.1.8. Sensor Lifetime Maintenance Demanded Limit S7 (Status; Diagnosis)
- 6.1.9. Device Service Maintenance Required Limit S8 (Status; Diagnosis)
- 6.1.10. Device Service Maintenance Demanded Limit S9 (Status; Diagnosis)
- 6.1.11. LTB Scale S10 (Status; Diagnosis)
- 6.1.12. Internal Temp Sensor S11 (Status; Diagnosis)
- 6.1.13. Internal Temp High S12 (Status; Diagnosis)
- 6.1.16. AIFB2 PV Range S15 (Status; Diagnosis)
- 6.1.19. Calibration Schedule Maintenance Demanded Limit S18 (Status; Diagnosis)
- 6.1.30. Memory EEPROM S29 (Status; Diagnosis)
- 6.1.31. Memory EEPROM Flags S30 (Status; Diagnosis)
- 6.1.32. Memory Flash S31 (Status; Diagnosis)
- 6.1.33. Ident Violation S32 (Status; Diagnosis)
- 6.1.34. Internal Temperature Calibration S33 (Status; Diagnosis)
- 6.1. Condensed Status Mode
- Appendix B: Technical Reference
- Appendix C: Troubleshooting
- Appendix D: Maintenance
- Appendix E: Software Revision History
- Glossary
- Index
Page 73 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
mmmmm
Parameters
3.1.6. Process Value Scale
3.1.6.1. Lower Value
Defines the operational lower range value of the input value (Process
Value Scale) in engineering units. Process Value Scale normalizes the
input value to a customer-defined range.
3.1.6.2. Upper Value
Defines the operational upper range value of the input value (Process
Value Scale) in engineering units. Process Value Scale normalizes the
input value to a customer-defined range.
3.1.7. Output Scale
Scales the Process Variable. The function block parameter OUT SCALE
contains the values of the lower limit and upper limit effective range.
3.1.7.1. Lower Value
Defines the operational lower range value of the output value in
engineering units.
3.1.7.2. Upper Value
Defines the operational upper range value of the output value in
engineering units.
3.1.8. Output Limits
3.1.8.1. Lower Limit Alarm
The setting for the lower alarm limit in engineering units.
3.1.8.2. Lower Limit Warning
The setting for the lower warning limit in engineering units.
3.1.8.3. Upper Limit Warning
The setting for the upper warning limit in engineering units.
3.1.8.4. Upper Limit Alarm
The setting for the upper alarm limit in engineering units
0
1
2
3
4
5
6
12345
Process Value Scale (typical
Input (0 to 100%)
Output Scale
Out (AIFB1 or AIFB2 Out)