G: Troubleshooting
S:8
Service interval as defined in
Maintenance Required Limit
has expired.
Perform service.
1
0
S:9
Service interval as defined in
Maintenance Demanded
Limit has expired.
Perform service.
1
S:10
Input parameters High
Calibration Point and Low
Calibration Point are the
same.
Check calibration settings of
device. Ensure settings for
High Calibration Point and
Low Calibration Point are
different.
3
S:11
Internal temperature sensor
failure.
Return the device to the
factory.
4
S:12 *
Internal temperature of the
device has exceeded
specifications: it is operating
outside its temperature
range.
Lower the ambient
temperature enough to cool
the device.
Fault code will persist until a
manual reset is performed
using PDM or the LCD
interface.
5
S:14
Upper and lower input values
(Process Value Scale) for
AIFB1 are the same.
Check configuration for
AIFB1. Ensure that Upper
Value and Lower Value
(Process Value Scale) are not
the same.
6
S:15
Upper and lower input values
(Process Value Scale) for
AIFB2 are the same.
Check configuration for
AIFB2. Ensure that Upper
Value and Lower Value
(Process Value Scale) are not
the same.
7
LCD
display
Meaning (cont’d) Corrective Action
Byte
(cont’d)
Bit