7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 95
mmmmm
Parameters
2.4.3. Minimum Sensor Value
Read only. Defines the minimum usable value for the measuring range, in units
defined in Unit (2.3.1.).
(Default = 0.0 m)
For access via AMS Device Manager see Range under Signal Processing (LTB)
on page 53
.
2.4.4. Maximum Sensor Value
Read only. Defines the maximum usable value for the measuring range, in units
defined in Unit (2.3.1.).
Default depends on device:
40 m device default = 45.0 m
100 m device default = 105 m)
For access via AMS Device Manager see Range under Signal Processing (LTB)
on page 53
.
2.4.5. Echo Select
2.4.5.1. Algorithm
Selects the algorithm to be applied to the echo profile to extract the true
echo.
Options
ALF
Area Largest First
A
Echo Area
L
Largest Echo
*F
First Echo
AL
Area Largest
AF
Area First
LF
Largest First
BLF
Best of First or Largest echo
BL
Best Largest
BF
Best First
LAST
TF
True First
sensor value (distance from sensor reference point
to the target)
sensor reference point (flange face)
Level