Page 110 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01
mmmmm
Parameters
4. Service
4.1. Master Reset
To perform a reset via AMS Device Manager:
see Master Reset on page 63 under
Operation (RESOURCE)
on page 62.
To perform a reset via local operation:
a) Press RIGHT Arrow to open Edit Mode then scroll down to the desired reset
type and press RIGHT Arrow to select it.
b) Press LEFT Arrow to exit.
After a master reset is performed, the device will stop measuring, the Resource and
Level Transducer Blocks will go to Out of Service, and the LCD will display the Quick
Start Wizard until the device is configured.
Note: Default settings in the parameter tables are indicated with an asterisk (*) unless
explicitly stated.
Notes:
The following parameters are not reset by any reset type: Write Protection, Auto
False Echo Suppression Range, Learned TVT.
While an FF Object Dictionary Reset is in progress, the Master Reset Parameter
View showing PREVIOUS/NEXT/BACK/EDIT options will be displayed. Do not
perform an action using the local display interface until the reset is complete
b)
.
This could cause a temporary loss of communications.
Reset Type Result
Factory
Defaults
a)
a)
The only difference between Factory Defaults and Functional reset is that Fac-
tory Defaults resets maintenance parameters, such as device and sensor wear,
calibration and maintenance timers. Functional reset does not reset these
parameters.
Default. Resets all user parameters to the manufacturer’s default
settings. Following this type of reset, complete reprogramming is
required.
Standard
Defaults
Resets all parameters to standard default settings.
Informational Resets parameters such as Block Descriptor, Strategy, Device
Install Date, Device Message.
Functional
a)
Resets parameters that control device behavior and functionality
(such as Low Calibration Point).
Warm Start Has the same effect as recycling power to the device.
FF Object
Dictionary
b)
b)
FF Object Dictionary reset completes with an automatic power cycle.
Resets all user parameters except for calibration to Factory
Defaults. This option also clears any function block parameters
and device schedule
c)
set by the user.
c)
See the manual
Foundation Fieldbus for Level instruments (7ML19985MP01)
,
Data Transmission, for more details.